Reference · Selectivity Study

How the selectivity study works

Documents → curves and tables we keep → rules → checks → the verdict. Every box opens its source, retained basis and use in the study.

← back to the study

Solid: the File menu’s DNO-fed route — BS 88-3 100 A → NSXm F TM100D → iC60H B16.

Solid: the File menu’s transformer-fed route — MTZ2 16 H1 6.0X → NSX250N 5.2 → iC60H C32.

Every document and rule in this section.

Documents we readCurves and tablesRulesChecksThe verdict Selectivity coordination guideSelectivity coordination … ComPacT NSX and NSXm catalogueComPacT NSX and NSXm cata… NSX thermal-magnetic user guideNSX thermal-magnetic user… NSX MicroLogic user guideNSX MicroLogic user guide MicroLogic X user guideMicroLogic X user guide MTZ with MicroLogic X catalogueMTZ with MicroLogic X cat… MTZ Active catalogueMTZ Active catalogue ComPact NS documentsComPact NS documents MasterPact NT and NW documentsMasterPact NT and NW docu… Acti9 Isobar UK catalogueActi9 Isobar UK catalogue Acti9 low voltage catalogueActi9 low voltage catalog… Acti9 iC40 catalogueActi9 iC40 catalogue iC60 tripping bands and FAQiC60 tripping bands and F… Multi9 OEM catalogueMulti9 OEM catalogue TeSys B6 cataloguesTeSys B6 catalogues TeSys GV4 guide and trip-class FAQTeSys GV4 guide and trip-… BS 7671 selectivity referencesBS 7671 selectivity refer… Guide tablesGuide tables TM-D and TM-G curvesTM-D and TM-G curves Energy-limit curvesEnergy-limit curves TeSys average curvesTeSys average curves iC60 tripping bandsiC60 tripping bands NSX and NSXm devicesNSX and NSXm devices MTZ devicesMTZ devices NS, NT and NW devicesNS, NT and NW devices Acti9 devicesActi9 devices Multi9 devicesMulti9 devices TeSys devicesTeSys devices Generic fuses and breakersGeneric fuses and breakers Device bands and hot upstreamDevice bands and hot upstream Curves, then tested tablesCurves, then tested tables Shown and probable overlapsShown and probable overlaps A missing edge proves nothingA missing edge proves nothing BS 88 fuse rating ratioBS 88 fuse rating ratio Residual-current coordinationResidual-current coordination Breaking-capacity boundBreaking-capacity bound TeSys trip-class guaranteeTeSys trip-class guarantee iC60 drawn feetiC60 drawn feet The wider magnetic bandThe wider magnetic band Phase faultsPhase faults Earth faultsEarth faults RCD pairRCD pair The study verdictThe study verdict LV System Designer — Build 2LV System Designer — Build 2

Documents

Curves and tables we keep

  • Guide tables — The guide holds 101 tables. Read upstream columns against downstream rows, subject to A-7/A-8. The reference library describes coverage and never reproduces a row or cell.
  • TM-D and TM-G curves — The 27 traced charts retain both published edges. Adjust the current scale for Ir and apply the H-3 hot-start correction upstream.
  • Energy-limit curves — Read published let-through only within the frame breaking capacity and stated voltage. Elsewhere energy is bounded by slowest time times current squared.
  • TeSys average curves — These are average curves, not tolerance bands. Stretch to the guaranteed trip-class point; assumed edges remain VERIFY.
  • iC60 tripping bands — Retain the published thermal edges and the separate C, D and K drawn feet. The magnetic range uses the wider printed range.
  • NSX and NSXm devices — The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
  • MTZ devices — The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
  • NS, NT and NW devices — The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
  • Acti9 devices — The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
  • Multi9 devices — The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
  • TeSys devices — The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
  • Generic fuses and breakers — The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.

Constants

    Rules

    • Device bands and hot upstream — Use the upstream fastest edge, hot at 0.9 × Ir, against the downstream slowest cold edge. Touching bands are selective.
    • Curves, then tested tables — Curves decide wherever one device takes at least 50 ms. Where both act faster, use the tested pair limit only when the guide conditions A-7 and A-8 hold.
    • Shown and probable overlaps — A shown overlap requires published edges. An overlap resting on an assumed edge is probable and gives review, including a stretched TeSys average or a generic envelope between anchors.
    • A missing edge proves nothing — A missing upstream fastest edge counts as instantaneous. Absence of overlap on an unpublished edge cannot establish a definite pass.
    • BS 88 fuse rating ratio — Annex A53 applies to BS 88 fuse-links of the same category, both at least 16 A: the rating ratio must reach 1.6:1. BS 3036 pairs use curves.
    • Residual-current coordination — Reg 536.4.1.4 governs RCD pairs. Between MicroLogic earth-leakage units use the manufacturer’s ratio of two and time condition; other pairs need a delayed upstream and ratio of three.
    • Breaking-capacity bound — A result cannot pass above the downstream breaking capacity. Reg 434.5.1 requires back-up protection there; this study does not verify it.
    • TeSys trip-class guarantee — The guaranteed point is the trip-class time at 7.2 × Ir. Extending that guarantee into a complete band requires assumptions, which remain VERIFY.
    • iC60 drawn feet — C, D and K have distinct drawn feet beyond the earlier magnetic band. Join each foot to the faster I²t extension; do not treat the missing common edge as published.
    • The wider magnetic band — Where two magnetic ranges are printed, retain the wider range. A narrower drawing does not override the printed pickup tolerances.

    Checks

    • Phase faults — Check each adjacent pair up to the fault level at the downstream board, combining published curves and eligible tested limits.
    • Earth faults — Combine phase and ground/residual functions. Guide tables cover phase faults only; an earth fault in the instantaneous region remains indicative. Ig and tg also need A-8.
    • RCD pair — Compare residual sensitivity and holding versus breaking time; report each failed condition. A route without two residual functions has no RCD pair check.

    Calculator

    • The study verdict — Total, selective up to a limit, not selective or review: the worst pair and check determine the route verdict. A capped scan never supplies a printed limit.
    • LV System Designer — Build 2 — Build 2 resolves the designer’s devices through the same library and study. Its board fault levels are computed by the designer; the standalone study uses entered levels.