Table we keep · Selectivity Study
Multi9 devices
estimatedsel.table.multi9-devices
The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
Retained data
The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
Read live through tools/selectivity/library/index.js · family. Catalogue rows, cells and curve coordinates are not reproduced.
How the calculator uses it
What the study keeps
C60 family ratings, printed magnetic settings, Vigi C60 and N40 Vigi residual functions from the OEM catalogue.
The supplemental Multi9 branch uses the same phase study as Acti9, with the Multi9-specific magnetic band. Its instantaneous zone remains indicative because no tested guide pair exists. See Multi9 OEM catalogue.
VERIFY
Icu is held; a BS EN 60898-1 Icn is not printed. No time-delayed Vigi C60 is offered by this catalogue.
Worked through on a Multi9 branch
| Pair | ComPacT NSX250N MicroLogic 5.2 E 250 A → Multi9 C60N B63 |
|---|---|
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Selective on the curves up to 2.55 kA, where both devices can trip instantaneously. Schneider's guide has no table for this pair, so above that it is indicative. |
| Phase status | review |
| VERIFY from this run | No tested table for this pair: the instantaneous zone is indicative (SPE-30 — no definite pass without a definite basis). |
Computed by the calculator for this run when this page was generated — not typed.