Document · Selectivity Study

Multi9 OEM catalogue

published

sel.doc.lvcatm9

Multi9 MCBs and residual modules; the guide has no Multi9 pair tables.

Local graph

Leans on · 0Leaned on by · 1NothingMulti9 devices — used to derive, estimatedMulti9 devicesused to deriveMulti9 OEM catalogue Leans on · 0Leaned on by · 1NothingMulti9 devices — used to derive, estimatedMulti9 devicesused to deriveMulti9 OEMcatalogue Leans on · 0Leaned on by · 1NothingMulti9 devices — used to derive, estimatedMulti9 devicesused to deriveMulti9 OEM catalogue

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The original document

Publisher
Schneider Electric
Title
LVCATM9OEM_EN — Multi9 OEM catalogue
Edition
April 2026, V2.2
Where in it
24–29, 44–45, 48–49
Do we hold it
Owner’s local copy; not distributed
May it be reproduced here
In small extracts, quoted with acknowledgement. The document is the authority.

Schneider document download ↗ We are not the source of record.

What the document says

Multi9 MCBs and residual modules; the guide has no Multi9 pair tables. See the original at 24–29, 44–45, 48–49; no extract is reproduced on this page.

How the calculator uses it

What the study keeps

The study retains the portions needed by Multi9 devices. Each retained dataset or method keeps the original source locator.

The source is used for multi9 MCBs and residual modules; the guide has no Multi9 pair tables. Follow the connected nodes to see the actual retained data and method, then the live worked result below.

VERIFY

Check April 2026, V2.2 against the actual device and current manufacturer instructions. Source pages: 24–29, 44–45, 48–49.

Worked through on a Multi9 branch

PairComPacT NSX250N MicroLogic 5.2 E 250 A → Multi9 C60N B63
Fault level at downstream board4.2 kA
Phase verdictSelective on the curves up to 2.55 kA, where both devices can trip instantaneously. Schneider's guide has no table for this pair, so above that it is indicative.
Phase statusreview
VERIFY from this runNo tested table for this pair: the instantaneous zone is indicative (SPE-30 — no definite pass without a definite basis).

Computed by the calculator for this run when this page was generated — not typed.