Rule · Selectivity Study
Device bands and hot upstream
estimatedsel.rule.device-bands
Use the upstream fastest edge, hot at 0.9 × Ir, against the downstream slowest cold edge. Touching bands are selective.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
What the study keeps
A function for the fastest operation and a function for certain clearing, together with evidence flags for each edge.
For each scan current compare downstream slowest clearing plus the chosen margin with upstream fastest operation. The upstream thermal image starts loaded; the downstream starts cold. See TM-D and TM-G curves, iC60 tripping bands, NSX and NSXm devices, MTZ devices, NS, NT and NW devices, Acti9 devices, Multi9 devices, TeSys devices, Generic fuses and breakers.
VERIFY
The band’s evidence flags matter as much as its shape. An illustrative lower edge cannot establish a definite pass.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.