Rule · Selectivity Study

Device bands and hot upstream

estimated

sel.rule.device-bands

Use the upstream fastest edge, hot at 0.9 × Ir, against the downstream slowest cold edge. Touching bands are selective.

Local graph

Leans on · 9Leaned on by · 4TM-D and TM-G curves — derived from, publishedTM-D and TM-G curvesderived fromiC60 tripping bands — derived from, publishediC60 tripping bandsderived fromNSX and NSXm devices — derived from, estimatedNSX and NSXm devicesderived fromMTZ devices — derived from, estimatedMTZ devicesderived fromNS, NT and NW devices — derived from, estimatedNS, NT and NW devicesderived fromActi9 devices — derived from, estimatedActi9 devicesderived fromMulti9 devices — derived from, estimatedMulti9 devicesderived fromTeSys devices — derived from, estimatedTeSys devicesderived fromGeneric fuses and breakers — derived from, estimatedGeneric fuses and breakersderived fromCurves, then tested tables — used to derive, estimatedCurves, then tested tablesused to deriveShown and probable overlaps — used to derive, estimatedShown and probableoverlapsused to deriveA missing edge proves nothing — used to derive, estimatedA missing edge provesnothingused to deriveBreaking-capacity bound — used to derive, estimatedBreaking-capacity boundused to deriveDevice bands and hotupstream Leans on · 9Leaned on by · 4TM-D and TM-G curves — derived from, publishedTM-D and TM-Gcurvesderived fromiC60 tripping bands — derived from, publishediC60 trippingbandsderived fromNSX and NSXm devices — derived from, estimatedNSX and NSXmdevicesderived fromMTZ devices — derived from, estimatedMTZ devicesderived fromNS, NT and NW devices — derived from, estimatedNS, NT and NWdevicesderived fromActi9 devices — derived from, estimatedActi9 devicesderived fromMulti9 devices — derived from, estimatedMulti9 devicesderived fromTeSys devices — derived from, estimatedTeSys devicesderived fromGeneric fuses and breakers — derived from, estimatedGeneric fuses andbreakersderived fromCurves, then tested tables — used to derive, estimatedCurves, thentested tablesused to deriveShown and probable overlaps — used to derive, estimatedShown andprobable overlapsused to deriveA missing edge proves nothing — used to derive, estimatedA missing edgeproves nothingused to deriveBreaking-capacity bound — used to derive, estimatedBreaking-capacityboundused to deriveDevice bandsand hotupstream Leans on · 9Leaned on by · 4TM-D and TM-G curves — derived from, publishedTM-D and TM-Gcurvesderived fromiC60 tripping bands — derived from, publishediC60 trippingbandsderived fromNSX and NSXm devices — derived from, estimatedNSX andNSXm devicesderived fromMTZ devices — derived from, estimatedMTZ devicesderived fromNS, NT and NW devices — derived from, estimatedNS, NT and NWdevicesderived fromActi9 devices — derived from, estimatedActi9 devicesderived fromMulti9 devices — derived from, estimatedMulti9 devicesderived fromTeSys devices — derived from, estimatedTeSys devicesderived fromGeneric fuses and breakers — derived from, estimatedGeneric fusesand breakersderived fromCurves, then tested tables — used to derive, estimatedCurves, thentested tablesused to deriveShown and probable overlaps — used to derive, estimatedShown andprobableoverlapsused to deriveA missing edge proves nothing — used to derive, estimatedA missing edgeproves nothingused to deriveBreaking-capacity bound — used to derive, estimatedBreaking-capacity boundused to deriveDevice bands and hot upstream

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

How the calculator uses it

What the study keeps

A function for the fastest operation and a function for certain clearing, together with evidence flags for each edge.

For each scan current compare downstream slowest clearing plus the chosen margin with upstream fastest operation. The upstream thermal image starts loaded; the downstream starts cold. See TM-D and TM-G curves, iC60 tripping bands, NSX and NSXm devices, MTZ devices, NS, NT and NW devices, Acti9 devices, Multi9 devices, TeSys devices, Generic fuses and breakers.

VERIFY

The band’s evidence flags matter as much as its shape. An illustrative lower edge cannot establish a definite pass.

Worked through on DNO-fed route

PairBS 88-3 100 A fuse → ComPacT NSXm F TM100D
Fault level at downstream board16 kA
Phase verdictNot selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published).
Phase statusfail
VERIFY from this runUpstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY).
PairComPacT NSXm F TM100D → Acti9 iC60H B16
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.