Table we keep · Selectivity Study
TeSys devices
estimatedsel.table.tesys-devices
The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
Retained data
The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
Read live through tools/selectivity/library/index.js · family. Catalogue rows, cells and curve coordinates are not reproduced.
How the calculator uses it
What the study keeps
GV2/GV3/GV4 references, overload dial ranges, magnetic settings, trip classes and breaking capacities.
The motor branch resolves a real GV2ME reference. Its thermal band uses the average curves and class point; a guide entry is usable only when the motor-protection ratios hold. See TeSys B6 catalogues, TeSys GV4 guide and trip-class FAQ.
VERIFY
Magnetic-only devices omit the overload relay. GV4P/PE borrow GV4PEM timing and tolerances as a stated assumption; check the actual device.
Worked through on a TeSys motor branch
| Pair | ComPacT NSX250N MicroLogic 5.2 E 250 A → TeSys GV2ME14 · 6–10 A |
|---|---|
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-108: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.