Table we keep · Selectivity Study

TeSys devices

estimated

sel.table.tesys-devices

The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.

Local graph

Leans on · 2Leaned on by · 1TeSys B6 catalogues — derived from, publishedTeSys B6 cataloguesderived fromTeSys GV4 guide and trip-class FAQ — derived from, publishedTeSys GV4 guide andtrip-class FAQderived fromDevice bands and hot upstream — used to derive, estimatedDevice bands and hotupstreamused to deriveTeSys devices Leans on · 2Leaned on by · 1TeSys B6 catalogues — derived from, publishedTeSys B6cataloguesderived fromTeSys GV4 guide and trip-class FAQ — derived from, publishedTeSys GV4 guideand trip-class FAQderived fromDevice bands and hot upstream — used to derive, estimatedDevice bands andhot upstreamused to deriveTeSys devices Leans on · 2Leaned on by · 1TeSys B6 catalogues — derived from, publishedTeSys B6cataloguesderived fromTeSys GV4 guide and trip-class FAQ — derived from, publishedTeSys GV4guide andtrip-class FAQderived fromDevice bands and hot upstream — used to derive, estimatedDevice bandsand hotupstreamused to deriveTeSys devices

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

Retained data

The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.

Read live through tools/selectivity/library/index.js · family. Catalogue rows, cells and curve coordinates are not reproduced.

How the calculator uses it

What the study keeps

GV2/GV3/GV4 references, overload dial ranges, magnetic settings, trip classes and breaking capacities.

The motor branch resolves a real GV2ME reference. Its thermal band uses the average curves and class point; a guide entry is usable only when the motor-protection ratios hold. See TeSys B6 catalogues, TeSys GV4 guide and trip-class FAQ.

VERIFY

Magnetic-only devices omit the overload relay. GV4P/PE borrow GV4PEM timing and tolerances as a stated assumption; check the actual device.

Worked through on a TeSys motor branch

PairComPacT NSX250N MicroLogic 5.2 E 250 A → TeSys GV2ME14 · 6–10 A
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-108: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.