Document · Selectivity Study

TeSys B6 catalogues

published

sel.doc.tesys-b6

Motor references, settings, breaking capacities and average operating curves.

Local graph

Leans on · 0Leaned on by · 2NothingTeSys average curves — used to derive, estimatedTeSys average curvesused to deriveTeSys devices — used to derive, estimatedTeSys devicesused to deriveTeSys B6 catalogues Leans on · 0Leaned on by · 2NothingTeSys average curves — used to derive, estimatedTeSys averagecurvesused to deriveTeSys devices — used to derive, estimatedTeSys devicesused to deriveTeSys B6catalogues Leans on · 0Leaned on by · 2NothingTeSys average curves — used to derive, estimatedTeSys averagecurvesused to deriveTeSys devices — used to derive, estimatedTeSys devicesused to deriveTeSys B6 catalogues

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The original document

Publisher
Schneider Electric
Title
TeSys B6 P and T — TeSys B6 catalogues
Edition
2026
Where in it
P B6/12–39; T B6/74–76, 83, 104–105, 109, 122–123, 129
Do we hold it
Owner’s local copy; not distributed
May it be reproduced here
In small extracts, quoted with acknowledgement. The document is the authority.

Schneider TeSys B6 technical catalogue ↗ We are not the source of record.

What the document says

Motor references, settings, breaking capacities and average operating curves. See the original at P B6/12–39; T B6/74–76, 83, 104–105, 109, 122–123, 129; no extract is reproduced on this page.

How the calculator uses it

What the study keeps

The study retains the portions needed by TeSys average curves; TeSys devices. Each retained dataset or method keeps the original source locator.

The source is used for motor references, settings, breaking capacities and average operating curves. Follow the connected nodes to see the actual retained data and method, then the live worked result below.

VERIFY

Check 2026 against the actual device and current manufacturer instructions. Source pages: P B6/12–39; T B6/74–76, 83, 104–105, 109, 122–123, 129.

Worked through on a TeSys motor branch

PairComPacT NSX250N MicroLogic 5.2 E 250 A → TeSys GV2ME14 · 6–10 A
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-108: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.