Table we keep · Selectivity Study
TeSys average curves
estimatedsel.table.tesys-curves
These are average curves, not tolerance bands. Stretch to the guaranteed trip-class point; assumed edges remain VERIFY.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
Retained data
These are average curves, not tolerance bands. Stretch to the guaranteed trip-class point; assumed edges remain VERIFY.
Read live through tools/selectivity/library/schneider/tesys-curves-data.js · TESYS_CURVES. Catalogue rows, cells and curve coordinates are not reproduced.
How the calculator uses it
What the study keeps
GV2, GV3P and GV4P average operating curves, including cold/hot states and the dial endpoints where separately drawn.
motorBand() scales the cold average to reach the trip-class guarantee and uses an assumed allowance on the hot curve. compareBands() distinguishes overlap on the average from overlap introduced only by that allowance. See TeSys B6 catalogues, TeSys GV4 guide and trip-class FAQ.
VERIFY
Average curves are not published tolerance bands. A probable overlap on an assumed edge is review, not a shown failure.
Worked through on a TeSys motor branch
| Pair | ComPacT NSX250N MicroLogic 5.2 E 250 A → TeSys GV2ME14 · 6–10 A |
|---|---|
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-108: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.