Document · Selectivity Study
TeSys GV4 guide and trip-class FAQ
publishedsel.doc.doca0118en
GV4 dial and timing; the FAQ guarantees a trip-class point for GV2/GV3.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The original document
- Publisher
- Schneider Electric
- Title
- DOCA0118EN; FAQ FA286067 — TeSys GV4 guide and trip-class FAQ
- Edition
- 01, 09/2019; FAQ modified 25/05/2025
- Where in it
- 25, 26, 30, 32; FAQ trip-class statement
- Do we hold it
- Owner’s local copy; not distributed
- May it be reproduced here
- In small extracts, quoted with acknowledgement. The document is the authority.
Schneider document download ↗ We are not the source of record.
What the document says
GV4 dial and timing; the FAQ guarantees a trip-class point for GV2/GV3. See the original at 25, 26, 30, 32; FAQ trip-class statement; no extract is reproduced on this page.
How the calculator uses it
What the study keeps
The study retains the portions needed by TeSys average curves; TeSys devices. Each retained dataset or method keeps the original source locator.
The source is used for gV4 dial and timing; the FAQ guarantees a trip-class point for GV2/GV3. Follow the connected nodes to see the actual retained data and method, then the live worked result below.
VERIFY
Check 01, 09/2019; FAQ modified 25/05/2025 against the actual device and current manufacturer instructions. Source pages: 25, 26, 30, 32; FAQ trip-class statement.
Schneider FAQ FA286067 is the companion source for the GV2/GV3 trip-class guarantee.
Worked through on a TeSys motor branch
| Pair | ComPacT NSX250N MicroLogic 5.2 E 250 A → TeSys GV2ME14 · 6–10 A |
|---|---|
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-108: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.