Document · Selectivity Study

TeSys GV4 guide and trip-class FAQ

published

sel.doc.doca0118en

GV4 dial and timing; the FAQ guarantees a trip-class point for GV2/GV3.

Local graph

Leans on · 0Leaned on by · 2NothingTeSys average curves — used to derive, estimatedTeSys average curvesused to deriveTeSys devices — used to derive, estimatedTeSys devicesused to deriveTeSys GV4 guide andtrip-class FAQ Leans on · 0Leaned on by · 2NothingTeSys average curves — used to derive, estimatedTeSys averagecurvesused to deriveTeSys devices — used to derive, estimatedTeSys devicesused to deriveTeSys GV4guide andtrip-class FAQ Leans on · 0Leaned on by · 2NothingTeSys average curves — used to derive, estimatedTeSys averagecurvesused to deriveTeSys devices — used to derive, estimatedTeSys devicesused to deriveTeSys GV4 guide and trip-classFAQ

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The original document

Publisher
Schneider Electric
Title
DOCA0118EN; FAQ FA286067 — TeSys GV4 guide and trip-class FAQ
Edition
01, 09/2019; FAQ modified 25/05/2025
Where in it
25, 26, 30, 32; FAQ trip-class statement
Do we hold it
Owner’s local copy; not distributed
May it be reproduced here
In small extracts, quoted with acknowledgement. The document is the authority.

Schneider document download ↗ We are not the source of record.

What the document says

GV4 dial and timing; the FAQ guarantees a trip-class point for GV2/GV3. See the original at 25, 26, 30, 32; FAQ trip-class statement; no extract is reproduced on this page.

How the calculator uses it

What the study keeps

The study retains the portions needed by TeSys average curves; TeSys devices. Each retained dataset or method keeps the original source locator.

The source is used for gV4 dial and timing; the FAQ guarantees a trip-class point for GV2/GV3. Follow the connected nodes to see the actual retained data and method, then the live worked result below.

VERIFY

Check 01, 09/2019; FAQ modified 25/05/2025 against the actual device and current manufacturer instructions. Source pages: 25, 26, 30, 32; FAQ trip-class statement.

Schneider FAQ FA286067 is the companion source for the GV2/GV3 trip-class guarantee.

Worked through on a TeSys motor branch

PairComPacT NSX250N MicroLogic 5.2 E 250 A → TeSys GV2ME14 · 6–10 A
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-108: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.