Rule · Selectivity Study

TeSys trip-class guarantee

estimated

sel.rule.trip-class

The guaranteed point is the trip-class time at 7.2 × Ir. Extending that guarantee into a complete band requires assumptions, which remain VERIFY.

Local graph

Leans on · 1Leaned on by · 1TeSys average curves — derived from, estimatedTeSys average curvesderived fromPhase faults — used to derive, estimatedPhase faultsused to deriveTeSys trip-classguarantee Leans on · 1Leaned on by · 1TeSys average curves — derived from, estimatedTeSys averagecurvesderived fromPhase faults — used to derive, estimatedPhase faultsused to deriveTeSys trip-classguarantee Leans on · 1Leaned on by · 1TeSys average curves — derived from, estimatedTeSys averagecurvesderived fromPhase faults — used to derive, estimatedPhase faultsused to deriveTeSys trip-class guarantee

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

How the calculator uses it

What the study keeps

The guaranteed class point and the traced average curves remain distinct inputs to motorBand().

The supplemental motor branch shows the effect of a class-bounded slowest edge. A probable overlap caused by stretching an average is reported separately from one shown on published data. See TeSys average curves.

VERIFY

The assumed allowance between guaranteed points is not a manufacturer tolerance. Verify trip class, dial setting and motor operating conditions.

Worked through on a TeSys motor branch

PairComPacT NSX250N MicroLogic 5.2 E 250 A → TeSys GV2ME14 · 6–10 A
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-108: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.