Check · Selectivity Study
Phase faults
estimatedsel.check.phase
Check each adjacent pair up to the fault level at the downstream board, combining published curves and eligible tested limits.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
What the study keeps
Adjacent resolved device pairs, downstream board fault levels, curve overlap intervals and any eligible guide match.
computeStudy() calls phasePair() for each successive pair. The A-66 worked run demonstrates a finite tested limit; the route verdict combines the pair results. See Curves, then tested tables, Shown and probable overlaps, A missing edge proves nothing, BS 88 fuse rating ratio, Breaking-capacity bound, TeSys trip-class guarantee, iC60 drawn feet, The wider magnetic band.
VERIFY
The fault level belongs to the downstream board. The standalone page does not calculate that level.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.