Calculator · Selectivity Study
The study verdict
estimatedsel.tool.verdict
Total, selective up to a limit, not selective or review: the worst pair and check determine the route verdict. A capped scan never supplies a printed limit.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
What the study keeps
The phase, earth and residual results of every adjacent pair, retaining the evidence and limitations that produced them.
computeStudy() takes failure before review, and review before pass. Total describes the tested phase range up to downstream breaking capacity; a finite limit is printed only when supported. See Phase faults, Earth faults, RCD pair, Energy-limit curves.
VERIFY
Read every pair and enabled check. A route can have a favourable phase result while its earth check remains indicative.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.