Calculator · Selectivity Study
LV System Designer — Build 2
estimatedsel.tool.lv-designer
Build 2 resolves the designer’s devices through the same library and study. Its board fault levels are computed by the designer; the standalone study uses entered levels.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
What the study keeps
The same study contract, not a second selectivity algorithm. The designer adapter supplies resolved devices and board fault levels.
Build 2 calls computeStudy() inside the LV designer. The standalone transformer example below demonstrates the shared engine; it is not a computed LV designer network. See The study verdict.
VERIFY
The standalone run uses entered fault levels. Verify the designer’s network, impedance assumptions and mapped device settings when using its result.
Worked through on Transformer-fed route
| Pair | MasterPacT MTZ2 16 H1 MicroLogic 6.0 X 1600 A → ComPacT NSX250N MicroLogic 5.2 E 250 A |
|---|---|
| Fault level at downstream board | 38 kA |
| Phase verdict | Total selectivity (Schneider p. A-88: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
| Earth verdict | Earth faults: selective on the curves up to 21.6 kA; above that both can trip instantaneously and the guide's tables cover phase faults only (p. A-75 note), so it is indicative. |
| Pair | ComPacT NSX250N MicroLogic 5.2 E 250 A → Acti9 iC60H C32 |
| Fault level at downstream board | 9.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-68: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.