Table we keep · Selectivity Study

Energy-limit curves

published

sel.table.energy-limits

Read published let-through only within the frame breaking capacity and stated voltage. Elsewhere energy is bounded by slowest time times current squared.

Local graph

Leans on · 1Leaned on by · 1ComPacT NSX and NSXm catalogue — derived from, publishedComPacT NSX and NSXmcataloguederived fromThe study verdict — used to derive, estimatedThe study verdictused to deriveEnergy-limit curves Leans on · 1Leaned on by · 1ComPacT NSX and NSXm catalogue — derived from, publishedComPacT NSXand NSXmcataloguederived fromThe study verdict — used to derive, estimatedThe study verdictused to deriveEnergy-limitcurves Leans on · 1Leaned on by · 1ComPacT NSX and NSXm catalogue — derived from, publishedComPacT NSXand NSXmcataloguederived fromThe study verdict — used to derive, estimatedThe studyverdictused to deriveEnergy-limit curves

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

Retained data

Read published let-through only within the frame breaking capacity and stated voltage. Elsewhere energy is bounded by slowest time times current squared.

Read live through tools/selectivity/library/schneider/limits-data.js · ENERGY_LIMITS. Catalogue rows, cells and curve coordinates are not reproduced.

How the calculator uses it

What the study keeps

Frame-specific energy-limiting curves at the catalogue voltage, each retaining its source page.

resolve() attaches the frame’s let-through points only within its Icu. The energy view compares let-through with cable withstand; this comparison does not replace pair selectivity. See ComPacT NSX and NSXm catalogue.

VERIFY

Check voltage and device breaking capacity. Without a published limit curve, the energy view uses an upper bound from the slowest clearing time.

Worked through on Transformer-fed route

PairMasterPacT MTZ2 16 H1 MicroLogic 6.0 X 1600 A → ComPacT NSX250N MicroLogic 5.2 E 250 A
Fault level at downstream board38 kA
Phase verdictTotal selectivity (Schneider p. A-88: T), up to the downstream device's breaking capacity.
Phase statuspass
Earth verdictEarth faults: selective on the curves up to 21.6 kA; above that both can trip instantaneously and the guide's tables cover phase faults only (p. A-75 note), so it is indicative.
PairComPacT NSX250N MicroLogic 5.2 E 250 A → Acti9 iC60H C32
Fault level at downstream board9.2 kA
Phase verdictTotal selectivity (Schneider p. A-68: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.