Document · Selectivity Study

ComPacT NSX and NSXm catalogue

published

sel.doc.lvped221001en

Frames, settings, thermal-magnetic bands and published let-through curves.

Local graph

Leans on · 0Leaned on by · 3NothingTM-D and TM-G curves — used to derive, publishedTM-D and TM-G curvesused to deriveEnergy-limit curves — used to derive, publishedEnergy-limit curvesused to deriveNSX and NSXm devices — used to derive, estimatedNSX and NSXm devicesused to deriveComPacT NSX andNSXm catalogue Leans on · 0Leaned on by · 3NothingTM-D and TM-G curves — used to derive, publishedTM-D and TM-Gcurvesused to deriveEnergy-limit curves — used to derive, publishedEnergy-limitcurvesused to deriveNSX and NSXm devices — used to derive, estimatedNSX and NSXmdevicesused to deriveComPacT NSXand NSXmcatalogue Leans on · 0Leaned on by · 3NothingTM-D and TM-G curves — used to derive, publishedTM-D and TM-Gcurvesused to deriveEnergy-limit curves — used to derive, publishedEnergy-limitcurvesused to deriveNSX and NSXm devices — used to derive, estimatedNSX andNSXm devicesused to deriveComPacT NSX and NSXmcatalogue

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The original document

Publisher
Schneider Electric
Title
LVPED221001EN — ComPacT NSX and NSXm catalogue
Edition
March 2026
Where in it
A-3, A-7, A-9; B-5–B-18; H-2–H-15 (H-3 hot start); H-22/H-23
Do we hold it
Owner’s local copy; not distributed
May it be reproduced here
In small extracts, quoted with acknowledgement. The document is the authority.

Schneider document download ↗ We are not the source of record.

What the document says

“For hot start (0.9 x Ir), divide max. time by 2, min. time by 4.”

Schneider Electric, LVPED221001EN — ComPacT NSX and NSXm catalogue, pp.H-3 — quoted.

How the calculator uses it

What the study keeps

The study retains the portions needed by TM-D and TM-G curves; Energy-limit curves; NSX and NSXm devices. Each retained dataset or method keeps the original source locator.

The source is used for frames, settings, thermal-magnetic bands and published let-through curves. Follow the connected nodes to see the actual retained data and method, then the live worked result below.

VERIFY

Check March 2026 against the actual device and current manufacturer instructions. Source pages: A-3, A-7, A-9; B-5–B-18; H-2–H-15 (H-3 hot start); H-22/H-23.

Worked through on DNO-fed route

PairBS 88-3 100 A fuse → ComPacT NSXm F TM100D
Fault level at downstream board16 kA
Phase verdictNot selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published).
Phase statusfail
VERIFY from this runUpstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY).
PairComPacT NSXm F TM100D → Acti9 iC60H B16
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.