Table we keep · Selectivity Study
TM-D and TM-G curves
publishedsel.table.tm-curves
The 27 traced charts retain both published edges. Adjust the current scale for Ir and apply the H-3 hot-start correction upstream.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
Retained data
The 27 traced charts retain both published edges. Adjust the current scale for Ir and apply the H-3 hot-start correction upstream.
Read live through tools/selectivity/library/schneider/tm-curves-data.js · TM_CHARTS. Catalogue rows, cells and curve coordinates are not reproduced.
How the calculator uses it
What the study keeps
Both vector-drawn edges are retained with the chart grid and source page, rather than replaced by a generic inverse-time curve.
tmBand() reads the chart at the effective Ir. The upstream hot-start correction changes the two edges differently; the magnetic tolerance and drawn tail then lead into reflex tripping. See ComPacT NSX and NSXm catalogue, NSX thermal-magnetic user guide.
VERIFY
Check the selected TM-D or TM-G rating and chart. TM-G dial steps not printed in the catalogue remain an assumption.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.