Table we keep · Selectivity Study
NSX and NSXm devices
estimatedsel.table.nsx-devices
The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
Retained data
The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
Read live through tools/selectivity/library/index.js · family. Catalogue rows, cells and curve coordinates are not reproduced.
How the calculator uses it
What the study keeps
NSX/NSXm frames, performance versions, TM-D/TM-G and MicroLogic trip units, their real dial steps and source pages.
resolve() snaps settings to the device’s published steps, builds the trip functions and guide key, and attaches an energy curve where held. The DNO run uses the fixed NSXm thermal-magnetic unit. See ComPacT NSX and NSXm catalogue, NSX thermal-magnetic user guide, NSX MicroLogic user guide.
VERIFY
Catalogue tolerances take precedence over conflicting user-guide values. Check the actual installed trip unit, especially fixed versus adjustable settings.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.