Document · Selectivity Study

NSX MicroLogic user guide

published

sel.doc.doca0188en

The long-time thermal image; catalogue tolerances take precedence where they differ.

Local graph

Leans on · 0Leaned on by · 1NothingNSX and NSXm devices — used to derive, estimatedNSX and NSXm devicesused to deriveNSX MicroLogic userguide Leans on · 0Leaned on by · 1NothingNSX and NSXm devices — used to derive, estimatedNSX and NSXmdevicesused to deriveNSX MicroLogicuser guide Leans on · 0Leaned on by · 1NothingNSX and NSXm devices — used to derive, estimatedNSX andNSXm devicesused to deriveNSX MicroLogic user guide

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The original document

Publisher
Schneider Electric
Title
DOCA0188EN — NSX MicroLogic user guide
Edition
03
Where in it
63
Do we hold it
Owner’s local copy; not distributed
May it be reproduced here
In small extracts, quoted with acknowledgement. The document is the authority.

Schneider document download ↗ We are not the source of record.

What the document says

The long-time thermal image; catalogue tolerances take precedence where they differ. See the original at 63; no extract is reproduced on this page.

How the calculator uses it

What the study keeps

The study retains the portions needed by NSX and NSXm devices. Each retained dataset or method keeps the original source locator.

The source is used for the long-time thermal image; catalogue tolerances take precedence where they differ. Follow the connected nodes to see the actual retained data and method, then the live worked result below.

VERIFY

Check 03 against the actual device and current manufacturer instructions. Source pages: 63.

Worked through on DNO-fed route

PairBS 88-3 100 A fuse → ComPacT NSXm F TM100D
Fault level at downstream board16 kA
Phase verdictNot selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published).
Phase statusfail
VERIFY from this runUpstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY).
PairComPacT NSXm F TM100D → Acti9 iC60H B16
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity.
Phase statuspass