Document · Selectivity Study
NSX MicroLogic user guide
publishedsel.doc.doca0188en
The long-time thermal image; catalogue tolerances take precedence where they differ.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The original document
- Publisher
- Schneider Electric
- Title
- DOCA0188EN — NSX MicroLogic user guide
- Edition
- 03
- Where in it
- 63
- Do we hold it
- Owner’s local copy; not distributed
- May it be reproduced here
- In small extracts, quoted with acknowledgement. The document is the authority.
Schneider document download ↗ We are not the source of record.
What the document says
The long-time thermal image; catalogue tolerances take precedence where they differ. See the original at 63; no extract is reproduced on this page.
How the calculator uses it
What the study keeps
The study retains the portions needed by NSX and NSXm devices. Each retained dataset or method keeps the original source locator.
The source is used for the long-time thermal image; catalogue tolerances take precedence where they differ. Follow the connected nodes to see the actual retained data and method, then the live worked result below.
VERIFY
Check 03 against the actual device and current manufacturer instructions. Source pages: 63.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.