Check · Selectivity Study
RCD pair
publishedsel.check.rcd-pair
Compare residual sensitivity and holding versus breaking time; report each failed condition. A route without two residual functions has no RCD pair check.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
What the study keeps
Only pairs in which both devices have an enabled residual-current function produce this check.
The supplemental residual example compares the sensitivities, upstream delay/type and holding time. rcdPair() reports each unmet condition rather than hiding it behind a single ratio. See Residual-current coordination.
VERIFY
An absent RCD-pair result means the pair did not qualify for the check, not that residual-current coordination was demonstrated.
Worked through on two generic residual devices
| Pair | RCBO type C 63 A (BS EN 61009) → RCBO type B 16 A (BS EN 61009) |
|---|---|
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Selective on the curves up to 315 A, where both devices can trip instantaneously. Schneider's guide has no table for this pair, so above that it is indicative. |
| Phase status | review |
| Earth verdict | Earth faults: selective on the curves up to 500 A; above that both can trip instantaneously and the guide's tables cover phase faults only (p. A-75 note), so it is indicative. |
| RCD verdict | RCDs selective: 300 mA time-delayed over 30 mA (ratio 10.0, 3:1 of Reg 536.4.1.4), and the upstream holds longer than the downstream takes to break. |
| VERIFY from this run | No tested table for this pair: the instantaneous zone is indicative (SPE-30 — no definite pass without a definite basis). |
Computed by the calculator for this run when this page was generated — not typed.