Rule · Selectivity Study
Residual-current coordination
publishedsel.rule.rcd-rule
Reg 536.4.1.4 governs RCD pairs. Between MicroLogic earth-leakage units use the manufacturer’s ratio of two and time condition; other pairs need a delayed upstream and ratio of three.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
What the study keeps
Residual current settings, selective/delayed type, and each device’s holding and breaking functions.
rcdPair() chooses the manufacturer rule only between qualifying MicroLogic units. Every other pair goes through the shared residual-current ratio/type check and the time condition. See BS 7671 selectivity references, Selectivity coordination guide.
VERIFY
The current ratio alone is insufficient. Confirm that the upstream holds longer than the downstream can take to clear.
Worked through on two generic residual devices
| Pair | RCBO type C 63 A (BS EN 61009) → RCBO type B 16 A (BS EN 61009) |
|---|---|
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Selective on the curves up to 315 A, where both devices can trip instantaneously. Schneider's guide has no table for this pair, so above that it is indicative. |
| Phase status | review |
| Earth verdict | Earth faults: selective on the curves up to 500 A; above that both can trip instantaneously and the guide's tables cover phase faults only (p. A-75 note), so it is indicative. |
| RCD verdict | RCDs selective: 300 mA time-delayed over 30 mA (ratio 10.0, 3:1 of Reg 536.4.1.4), and the upstream holds longer than the downstream takes to break. |
| VERIFY from this run | No tested table for this pair: the instantaneous zone is indicative (SPE-30 — no definite pass without a definite basis). |
Computed by the calculator for this run when this page was generated — not typed.