Reg 536.4.1.4 governs RCD pairs. Between MicroLogic earth-leakage units use the manufacturer’s ratio of two and time condition; other pairs need a delayed upstream and ratio of three.

Local graph

Leans on · 2Leaned on by · 1BS 7671 selectivity references — derived from, publishedBS 7671 selectivityreferencesderived fromSelectivity coordination guide — derived from, publishedSelectivity coordinationguidederived fromRCD pair — used to derive, publishedRCD pairused to deriveResidual-currentcoordination Leans on · 2Leaned on by · 1BS 7671 selectivity references — derived from, publishedBS 7671selectivityreferencesderived fromSelectivity coordination guide — derived from, publishedSelectivitycoordination guidederived fromRCD pair — used to derive, publishedRCD pairused to deriveResidual-currentcoordination Leans on · 2Leaned on by · 1BS 7671 selectivity references — derived from, publishedBS 7671selectivityreferencesderived fromSelectivity coordination guide — derived from, publishedSelectivitycoordinationguidederived fromRCD pair — used to derive, publishedRCD pairused to deriveResidual-current coordination

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

How the calculator uses it

What the study keeps

Residual current settings, selective/delayed type, and each device’s holding and breaking functions.

rcdPair() chooses the manufacturer rule only between qualifying MicroLogic units. Every other pair goes through the shared residual-current ratio/type check and the time condition. See BS 7671 selectivity references, Selectivity coordination guide.

VERIFY

The current ratio alone is insufficient. Confirm that the upstream holds longer than the downstream can take to clear.

Worked through on two generic residual devices

PairRCBO type C 63 A (BS EN 61009) → RCBO type B 16 A (BS EN 61009)
Fault level at downstream board4.2 kA
Phase verdictSelective on the curves up to 315 A, where both devices can trip instantaneously. Schneider's guide has no table for this pair, so above that it is indicative.
Phase statusreview
Earth verdictEarth faults: selective on the curves up to 500 A; above that both can trip instantaneously and the guide's tables cover phase faults only (p. A-75 note), so it is indicative.
RCD verdictRCDs selective: 300 mA time-delayed over 30 mA (ratio 10.0, 3:1 of Reg 536.4.1.4), and the upstream holds longer than the downstream takes to break.
VERIFY from this runNo tested table for this pair: the instantaneous zone is indicative (SPE-30 — no definite pass without a definite basis).