Document · Selectivity Study

BS 7671 selectivity references

published

sel.doc.bs7671

Cited only: generic protective devices, breaking capacity and selectivity requirements.

Local graph

Leans on · 0Leaned on by · 4NothingGeneric fuses and breakers — used to derive, estimatedGeneric fuses and breakersused to deriveBS 88 fuse rating ratio — used to derive, estimatedBS 88 fuse rating ratioused to deriveResidual-current coordination — used to derive, publishedResidual-currentcoordinationused to deriveBreaking-capacity bound — used to derive, estimatedBreaking-capacity boundused to deriveBS 7671 selectivityreferences Leans on · 0Leaned on by · 4NothingGeneric fuses and breakers — used to derive, estimatedGeneric fuses andbreakersused to deriveBS 88 fuse rating ratio — used to derive, estimatedBS 88 fuse ratingratioused to deriveResidual-current coordination — used to derive, publishedResidual-currentcoordinationused to deriveBreaking-capacity bound — used to derive, estimatedBreaking-capacityboundused to deriveBS 7671selectivityreferences Leans on · 0Leaned on by · 4NothingGeneric fuses and breakers — used to derive, estimatedGeneric fusesand breakersused to deriveBS 88 fuse rating ratio — used to derive, estimatedBS 88 fuserating ratioused to deriveResidual-current coordination — used to derive, publishedResidual-currentcoordinationused to deriveBreaking-capacity bound — used to derive, estimatedBreaking-capacity boundused to deriveBS 7671 selectivity references

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The original document

Publisher
BSI / IET
Title
BS 7671:2018+A4:2026 — BS 7671 selectivity references
Edition
A4:2026
Where in it
Appendix 3 Figs 3A1–3A6; Table 41.3; Regs 433.1, 434.5.1, 536.4.1.2–536.4.1.4; Annex A53
Do we hold it
Owner’s local copy; not distributed
May it be reproduced here
No. BSI copyright — cited, never reproduced. Get it from BSI.

What the document says

Cited only: generic protective devices, breaking capacity and selectivity requirements. See the original at Appendix 3 Figs 3A1–3A6; Table 41.3; Regs 433.1, 434.5.1, 536.4.1.2–536.4.1.4; Annex A53; no extract is reproduced on this page.

How the calculator uses it

What the study keeps

The study retains the portions needed by Generic fuses and breakers; BS 88 fuse rating ratio; Residual-current coordination; Breaking-capacity bound. Each retained dataset or method keeps the original source locator.

The source is used for cited only: generic protective devices, breaking capacity and selectivity requirements. Follow the connected nodes to see the actual retained data and method, then the live worked result below.

VERIFY

Check the current licensed edition and cited clauses. This page reproduces no standard text, table or image.

IEC/EN 60947-2, BS EN 60898-1, IEC 60269-1, BS EN 61009-1 and IEC 60947-4-1 are named by the study but are not held.

Worked through on DNO-fed route

PairBS 88-3 100 A fuse → ComPacT NSXm F TM100D
Fault level at downstream board16 kA
Phase verdictNot selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published).
Phase statusfail
VERIFY from this runUpstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY).
PairComPacT NSXm F TM100D → Acti9 iC60H B16
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.