Document · Selectivity Study
BS 7671 selectivity references
publishedsel.doc.bs7671
Cited only: generic protective devices, breaking capacity and selectivity requirements.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The original document
- Publisher
- BSI / IET
- Title
- BS 7671:2018+A4:2026 — BS 7671 selectivity references
- Edition
- A4:2026
- Where in it
- Appendix 3 Figs 3A1–3A6; Table 41.3; Regs 433.1, 434.5.1, 536.4.1.2–536.4.1.4; Annex A53
- Do we hold it
- Owner’s local copy; not distributed
- May it be reproduced here
- No. BSI copyright — cited, never reproduced. Get it from BSI.
What the document says
Cited only: generic protective devices, breaking capacity and selectivity requirements. See the original at Appendix 3 Figs 3A1–3A6; Table 41.3; Regs 433.1, 434.5.1, 536.4.1.2–536.4.1.4; Annex A53; no extract is reproduced on this page.
How the calculator uses it
What the study keeps
The study retains the portions needed by Generic fuses and breakers; BS 88 fuse rating ratio; Residual-current coordination; Breaking-capacity bound. Each retained dataset or method keeps the original source locator.
The source is used for cited only: generic protective devices, breaking capacity and selectivity requirements. Follow the connected nodes to see the actual retained data and method, then the live worked result below.
VERIFY
Check the current licensed edition and cited clauses. This page reproduces no standard text, table or image.
IEC/EN 60947-2, BS EN 60898-1, IEC 60269-1, BS EN 61009-1 and IEC 60947-4-1 are named by the study but are not held.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.