Rule · Selectivity Study
BS 88 fuse rating ratio
estimatedsel.rule.fuse-ratio
Annex A53 applies to BS 88 fuse-links of the same category, both at least 16 A: the rating ratio must reach 1.6:1. BS 3036 pairs use curves.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
What the study keeps
A pointer to the shared fuseSelectivity implementation, with BS 88 family and category eligibility checked in the study.
The supplemental fuse run uses two eligible BS 88 links. The ratio rule is separate from the curve-overlap and breaking-capacity checks; a mixed or BS 3036 pair cannot inherit it. See BS 7671 selectivity references, Generic fuses and breakers.
VERIFY
Confirm both links’ utilization category and eligibility under Annex A53. It is an informative rule, not a generic breaker-to-fuse ratio.
Worked through on two BS 88 fuse-links
| Pair | BS 88-2 100 A fuse → BS 88-2 63 A fuse |
|---|---|
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Ratio 1.59:1 is below the 1.6:1 of Annex A53.4 — selectivity is not indicated. Increase the rating step, or compare the published I²t values. |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
Computed by the calculator for this run when this page was generated — not typed.