Table we keep · Selectivity Study

Generic fuses and breakers

estimated

sel.table.generic-devices

The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.

Local graph

Leans on · 1Leaned on by · 2BS 7671 selectivity references — derived from, publishedBS 7671 selectivityreferencesderived fromDevice bands and hot upstream — used to derive, estimatedDevice bands and hotupstreamused to deriveBS 88 fuse rating ratio — used to derive, estimatedBS 88 fuse rating ratioused to deriveGeneric fuses andbreakers Leans on · 1Leaned on by · 2BS 7671 selectivity references — derived from, publishedBS 7671selectivityreferencesderived fromDevice bands and hot upstream — used to derive, estimatedDevice bands andhot upstreamused to deriveBS 88 fuse rating ratio — used to derive, estimatedBS 88 fuse ratingratioused to deriveGeneric fusesand breakers Leans on · 1Leaned on by · 2BS 7671 selectivity references — derived from, publishedBS 7671selectivityreferencesderived fromDevice bands and hot upstream — used to derive, estimatedDevice bandsand hotupstreamused to deriveBS 88 fuse rating ratio — used to derive, estimatedBS 88 fuserating ratioused to deriveGeneric fuses and breakers

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

Retained data

The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.

Read live through tools/selectivity/library/index.js · MAKERS. Catalogue rows, cells and curve coordinates are not reproduced.

How the calculator uses it

What the study keeps

Generic fuse slowest points and modular breaker anchors cited to BS 7671, plus explicit flags for assumed or missing edges.

The DNO route’s cut-out uses this library. The same resolver supplies generic MCB and RCBO bands; the fuse and residual examples exercise their separate pair rules. See BS 7671 selectivity references.

VERIFY

Fuse pre-arcing gates and conventional times remain VERIFY. Breaking capacities are not supplied by BS 7671; enter and verify the actual device rating.

Worked through on DNO-fed route

PairBS 88-3 100 A fuse → ComPacT NSXm F TM100D
Fault level at downstream board16 kA
Phase verdictNot selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published).
Phase statusfail
VERIFY from this runUpstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY).
PairComPacT NSXm F TM100D → Acti9 iC60H B16
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.