Table we keep · Selectivity Study
Generic fuses and breakers
estimatedsel.table.generic-devices
The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
Retained data
The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
Read live through tools/selectivity/library/index.js · MAKERS. Catalogue rows, cells and curve coordinates are not reproduced.
How the calculator uses it
What the study keeps
Generic fuse slowest points and modular breaker anchors cited to BS 7671, plus explicit flags for assumed or missing edges.
The DNO route’s cut-out uses this library. The same resolver supplies generic MCB and RCBO bands; the fuse and residual examples exercise their separate pair rules. See BS 7671 selectivity references.
VERIFY
Fuse pre-arcing gates and conventional times remain VERIFY. Breaking capacities are not supplied by BS 7671; enter and verify the actual device rating.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.