Combine phase and ground/residual functions. Guide tables cover phase faults only; an earth fault in the instantaneous region remains indicative. Ig and tg also need A-8.

Local graph

Leans on · 2Leaned on by · 1Phase faults — derived from, estimatedPhase faultsderived fromSelectivity coordination guide — derived from, publishedSelectivity coordinationguidederived fromThe study verdict — used to derive, estimatedThe study verdictused to deriveEarth faults Leans on · 2Leaned on by · 1Phase faults — derived from, estimatedPhase faultsderived fromSelectivity coordination guide — derived from, publishedSelectivitycoordination guidederived fromThe study verdict — used to derive, estimatedThe study verdictused to deriveEarth faults Leans on · 2Leaned on by · 1Phase faults — derived from, estimatedPhase faultsderived fromSelectivity coordination guide — derived from, publishedSelectivitycoordinationguidederived fromThe study verdict — used to derive, estimatedThe studyverdictused to deriveEarth faults

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

How the calculator uses it

What the study keeps

The union of phase and enabled ground/residual functions for each device, and the entered earth-fault range.

earthPair() compares the combined functions across the range. Both ground functions also need the guide’s pickup ratio and time-band separation. See Phase faults, Selectivity coordination guide.

VERIFY

Phase tables cannot prove the instantaneous earth-fault region. Missing earth-fault ranges leave that part of the study unconfirmed.

Worked through on Transformer-fed route

PairMasterPacT MTZ2 16 H1 MicroLogic 6.0 X 1600 A → ComPacT NSX250N MicroLogic 5.2 E 250 A
Fault level at downstream board38 kA
Phase verdictTotal selectivity (Schneider p. A-88: T), up to the downstream device's breaking capacity.
Phase statuspass
Earth verdictEarth faults: selective on the curves up to 21.6 kA; above that both can trip instantaneously and the guide's tables cover phase faults only (p. A-75 note), so it is indicative.
PairComPacT NSX250N MicroLogic 5.2 E 250 A → Acti9 iC60H C32
Fault level at downstream board9.2 kA
Phase verdictTotal selectivity (Schneider p. A-68: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.