Check · Selectivity Study
Earth faults
estimatedsel.check.earth
Combine phase and ground/residual functions. Guide tables cover phase faults only; an earth fault in the instantaneous region remains indicative. Ig and tg also need A-8.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
What the study keeps
The union of phase and enabled ground/residual functions for each device, and the entered earth-fault range.
earthPair() compares the combined functions across the range. Both ground functions also need the guide’s pickup ratio and time-band separation. See Phase faults, Selectivity coordination guide.
VERIFY
Phase tables cannot prove the instantaneous earth-fault region. Missing earth-fault ranges leave that part of the study unconfirmed.
Worked through on Transformer-fed route
| Pair | MasterPacT MTZ2 16 H1 MicroLogic 6.0 X 1600 A → ComPacT NSX250N MicroLogic 5.2 E 250 A |
|---|---|
| Fault level at downstream board | 38 kA |
| Phase verdict | Total selectivity (Schneider p. A-88: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
| Earth verdict | Earth faults: selective on the curves up to 21.6 kA; above that both can trip instantaneously and the guide's tables cover phase faults only (p. A-75 note), so it is indicative. |
| Pair | ComPacT NSX250N MicroLogic 5.2 E 250 A → Acti9 iC60H C32 |
| Fault level at downstream board | 9.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-68: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.