Rule · Selectivity Study
A missing edge proves nothing
estimatedsel.rule.missing-edge
A missing upstream fastest edge counts as instantaneous. Absence of overlap on an unpublished edge cannot establish a definite pass.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
What the study keeps
An explicit absence of the upstream fastest edge and a separate check for whether a known edge is published.
An absent fastest edge is treated as able to trip immediately. If the curves stay separate only on an assumed edge, phasePair() still returns review. See Device bands and hot upstream.
VERIFY
A clean-looking gap on the chart is insufficient when its boundary is missing or illustrative. Obtain a published band or a valid tested pair basis.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.