Rule · Selectivity Study
Shown and probable overlaps
estimatedsel.rule.published-overlaps
A shown overlap requires published edges. An overlap resting on an assumed edge is probable and gives review, including a stretched TeSys average or a generic envelope between anchors.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
What the study keeps
Published/VERIFY/illustrative edge labels, the nominal slowest edge where available, and shown/probable overlap intervals.
compareBands() requires evidence on both sides of an overlap. A TeSys allowance or a generic envelope between anchors cannot turn an otherwise unshown overlap into a definite failure. See Device bands and hot upstream.
VERIFY
Review the basis of each edge. The run notes identify a probable overlap and an overlap caused only by hot upstream loading.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.