Rule · Selectivity Study

Curves, then tested tables

estimated

sel.rule.fifty-ms

Curves decide wherever one device takes at least 50 ms. Where both act faster, use the tested pair limit only when the guide conditions A-7 and A-8 hold.

Local graph

Leans on · 2Leaned on by · 1Device bands and hot upstream — derived from, estimatedDevice bands and hotupstreamderived fromGuide tables — derived from, publishedGuide tablesderived fromPhase faults — used to derive, estimatedPhase faultsused to deriveCurves, then testedtables Leans on · 2Leaned on by · 1Device bands and hot upstream — derived from, estimatedDevice bands andhot upstreamderived fromGuide tables — derived from, publishedGuide tablesderived fromPhase faults — used to derive, estimatedPhase faultsused to deriveCurves, thentested tables Leans on · 2Leaned on by · 1Device bands and hot upstream — derived from, estimatedDevice bandsand hotupstreamderived fromGuide tables — derived from, publishedGuide tablesderived fromPhase faults — used to derive, estimatedPhase faultsused to deriveCurves, then tested tables

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

How the calculator uses it

What the study keeps

The instantaneous-region boundary from study.js and the tested-table conditions from tables.js, rather than a second set of thresholds.

phasePair() follows the curves until both devices can act in the instantaneous region. It then applies the matched guide result only after conditions() accepts the settings. See Device bands and hot upstream, Guide tables.

VERIFY

Missing tables, unmet conditions and unsupported modes leave the instantaneous region indicative. No curve extrapolation supplies a substitute tested limit.

Worked through on DNO-fed route

PairBS 88-3 100 A fuse → ComPacT NSXm F TM100D
Fault level at downstream board16 kA
Phase verdictNot selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published).
Phase statusfail
VERIFY from this runUpstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY).
PairComPacT NSXm F TM100D → Acti9 iC60H B16
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.