Curves decide wherever one device takes at least 50 ms. Where both act faster, use the tested pair limit only when the guide conditions A-7 and A-8 hold.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
What the study keeps
The instantaneous-region boundary from study.js and the tested-table conditions from tables.js, rather than a second set of thresholds.
phasePair() follows the curves until both devices can act in the instantaneous region. It then applies the matched guide result only after conditions() accepts the settings. See Device bands and hot upstream, Guide tables.
VERIFY
Missing tables, unmet conditions and unsupported modes leave the instantaneous region indicative. No curve extrapolation supplies a substitute tested limit.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |