Table we keep · Selectivity Study
Guide tables
publishedsel.table.guide-tables
The guide holds 101 tables. Read upstream columns against downstream rows, subject to A-7/A-8. The reference library describes coverage and never reproduces a row or cell.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
Retained data
The guide holds 101 tables. Read upstream columns against downstream rows, subject to A-7/A-8. The reference library describes coverage and never reproduces a row or cell.
Read live through tools/selectivity/library/schneider/tables-data.js · TABLES. Catalogue rows, cells and curve coordinates are not reproduced.
How the calculator uses it
What the study keeps
The upstream label, device versions, trip-unit mode, downstream group and printed page remain attached to each table. The original unit is retained so amperes and kiloamperes cannot be confused.
lookup() matches the resolved pair and chooses the lower upstream setting column where the setting falls between columns. conditions() then gates the result. A total indication is bounded by downstream breaking capacity; a missing pair remains review. See Selectivity coordination guide.
VERIFY
Confirm the exact frame, version, trip unit, poles and settings against A-7 and A-8. No tested phase result establishes earth-fault selectivity.
Worked through on the guide’s A-66 example
| Pair | ComPacT NSX100F TM100D → Acti9 iC60N C32 |
|---|---|
| Fault level at downstream board | 10 kA |
| Phase verdict | Selective up to 1 kA (Schneider p. A-66). The fault level is 10 kA. |
| Phase status | fail |
Computed by the calculator for this run when this page was generated — not typed.