Table we keep · Selectivity Study

Guide tables

published

sel.table.guide-tables

The guide holds 101 tables. Read upstream columns against downstream rows, subject to A-7/A-8. The reference library describes coverage and never reproduces a row or cell.

Local graph

Leans on · 1Leaned on by · 1Selectivity coordination guide — derived from, publishedSelectivity coordinationguidederived fromCurves, then tested tables — used to derive, estimatedCurves, then tested tablesused to deriveGuide tables Leans on · 1Leaned on by · 1Selectivity coordination guide — derived from, publishedSelectivitycoordination guidederived fromCurves, then tested tables — used to derive, estimatedCurves, thentested tablesused to deriveGuide tables Leans on · 1Leaned on by · 1Selectivity coordination guide — derived from, publishedSelectivitycoordinationguidederived fromCurves, then tested tables — used to derive, estimatedCurves, thentested tablesused to deriveGuide tables

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

Retained data

The guide holds 101 tables. Read upstream columns against downstream rows, subject to A-7/A-8. The reference library describes coverage and never reproduces a row or cell.

Read live through tools/selectivity/library/schneider/tables-data.js · TABLES. Catalogue rows, cells and curve coordinates are not reproduced.

How the calculator uses it

What the study keeps

The upstream label, device versions, trip-unit mode, downstream group and printed page remain attached to each table. The original unit is retained so amperes and kiloamperes cannot be confused.

lookup() matches the resolved pair and chooses the lower upstream setting column where the setting falls between columns. conditions() then gates the result. A total indication is bounded by downstream breaking capacity; a missing pair remains review. See Selectivity coordination guide.

VERIFY

Confirm the exact frame, version, trip unit, poles and settings against A-7 and A-8. No tested phase result establishes earth-fault selectivity.

Worked through on the guide’s A-66 example

PairComPacT NSX100F TM100D → Acti9 iC60N C32
Fault level at downstream board10 kA
Phase verdictSelective up to 1 kA (Schneider p. A-66). The fault level is 10 kA.
Phase statusfail

Computed by the calculator for this run when this page was generated — not typed.