Rule · Selectivity Study

The wider magnetic band

estimated

sel.rule.magnetic-band

Where two magnetic ranges are printed, retain the wider range. A narrower drawing does not override the printed pickup tolerances.

Local graph

Leans on · 2Leaned on by · 1iC60 tripping bands — derived from, publishediC60 tripping bandsderived fromMulti9 devices — derived from, estimatedMulti9 devicesderived fromPhase faults — used to derive, estimatedPhase faultsused to deriveThe wider magneticband Leans on · 2Leaned on by · 1iC60 tripping bands — derived from, publishediC60 trippingbandsderived fromMulti9 devices — derived from, estimatedMulti9 devicesderived fromPhase faults — used to derive, estimatedPhase faultsused to deriveThe widermagnetic band Leans on · 2Leaned on by · 1iC60 tripping bands — derived from, publishediC60 trippingbandsderived fromMulti9 devices — derived from, estimatedMulti9 devicesderived fromPhase faults — used to derive, estimatedPhase faultsused to deriveThe wider magnetic band

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

How the calculator uses it

What the study keeps

Pickup limits as printed for the relevant standard and device family, including tolerance where the catalogue gives it.

The magnetic interval spans the wider of the applicable printed ranges. The phase comparison then covers the earliest upstream operation and latest downstream clearing. See iC60 tripping bands, Multi9 devices.

VERIFY

Check both printed ranges and their reference conditions. Do not narrow the interval to the position of a line in a diagram.

Worked through on DNO-fed route

PairBS 88-3 100 A fuse → ComPacT NSXm F TM100D
Fault level at downstream board16 kA
Phase verdictNot selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published).
Phase statusfail
VERIFY from this runUpstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY).
PairComPacT NSXm F TM100D → Acti9 iC60H B16
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.