Table we keep · Selectivity Study
iC60 tripping bands
publishedsel.table.ic60-bands
Retain the published thermal edges and the separate C, D and K drawn feet. The magnetic range uses the wider printed range.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
Retained data
Retain the published thermal edges and the separate C, D and K drawn feet. The magnetic range uses the wider printed range.
Read live through tools/selectivity/library/schneider/acti9-curves-data.js · ACTI9_CURVES. Catalogue rows, cells and curve coordinates are not reproduced.
How the calculator uses it
What the study keeps
Thermal band edges for the separately drawn rating groups and curves, with the distinct C, D and K feet.
mcbBand() interpolates the published edges and joins the selected curve’s foot. The magnetic step is supplied by the printed pickup range, not by measuring the drawn vertical. See iC60 tripping bands and FAQ.
VERIFY
Check rating group, curve and reference temperature. The FAQ supports the old drawing; it does not supply a new tolerance band.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.