Document · Selectivity Study

iC60 tripping bands and FAQ

published

sel.doc.ca908024e

Published thermal bands, C/D/K feet and the FAQ reading of the same drawing.

Local graph

Leans on · 0Leaned on by · 2NothingiC60 tripping bands — used to derive, publishediC60 tripping bandsused to deriveActi9 devices — used to derive, estimatedActi9 devicesused to deriveiC60 tripping bandsand FAQ Leans on · 0Leaned on by · 2NothingiC60 tripping bands — used to derive, publishediC60 trippingbandsused to deriveActi9 devices — used to derive, estimatedActi9 devicesused to deriveiC60 trippingbands and FAQ Leans on · 0Leaned on by · 2NothingiC60 tripping bands — used to derive, publishediC60 trippingbandsused to deriveActi9 devices — used to derive, estimatedActi9 devicesused to deriveiC60 tripping bands and FAQ

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The original document

Publisher
Schneider Electric
Title
CA908024E; FAQ FA346069 — iC60 tripping bands and FAQ
Edition
v2.8, 25/03/2014; FAQ modified 31/07/2025
Where in it
501, 503; FAQ attachment pp.517–518
Do we hold it
Owner’s local copy; not distributed
May it be reproduced here
In small extracts, quoted with acknowledgement. The document is the authority.

Schneider document download ↗ We are not the source of record.

What the document says

Published thermal bands, C/D/K feet and the FAQ reading of the same drawing. See the original at 501, 503; FAQ attachment pp.517–518; no extract is reproduced on this page.

How the calculator uses it

What the study keeps

The study retains the portions needed by iC60 tripping bands; Acti9 devices. Each retained dataset or method keeps the original source locator.

The source is used for published thermal bands, C/D/K feet and the FAQ reading of the same drawing. Follow the connected nodes to see the actual retained data and method, then the live worked result below.

VERIFY

Check v2.8, 25/03/2014; FAQ modified 31/07/2025 against the actual device and current manufacturer instructions. Source pages: 501, 503; FAQ attachment pp.517–518.

Schneider FAQ FA346069 attaches the drawing and explains how to read it.

Worked through on DNO-fed route

PairBS 88-3 100 A fuse → ComPacT NSXm F TM100D
Fault level at downstream board16 kA
Phase verdictNot selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published).
Phase statusfail
VERIFY from this runUpstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY).
PairComPacT NSXm F TM100D → Acti9 iC60H B16
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.