Document · Selectivity Study
iC60 tripping bands and FAQ
publishedsel.doc.ca908024e
Published thermal bands, C/D/K feet and the FAQ reading of the same drawing.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The original document
- Publisher
- Schneider Electric
- Title
- CA908024E; FAQ FA346069 — iC60 tripping bands and FAQ
- Edition
- v2.8, 25/03/2014; FAQ modified 31/07/2025
- Where in it
- 501, 503; FAQ attachment pp.517–518
- Do we hold it
- Owner’s local copy; not distributed
- May it be reproduced here
- In small extracts, quoted with acknowledgement. The document is the authority.
Schneider document download ↗ We are not the source of record.
What the document says
Published thermal bands, C/D/K feet and the FAQ reading of the same drawing. See the original at 501, 503; FAQ attachment pp.517–518; no extract is reproduced on this page.
How the calculator uses it
What the study keeps
The study retains the portions needed by iC60 tripping bands; Acti9 devices. Each retained dataset or method keeps the original source locator.
The source is used for published thermal bands, C/D/K feet and the FAQ reading of the same drawing. Follow the connected nodes to see the actual retained data and method, then the live worked result below.
VERIFY
Check v2.8, 25/03/2014; FAQ modified 31/07/2025 against the actual device and current manufacturer instructions. Source pages: 501, 503; FAQ attachment pp.517–518.
Schneider FAQ FA346069 attaches the drawing and explains how to read it.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.