Table we keep · Selectivity Study

Acti9 devices

estimated

sel.table.acti9-devices

The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.

Local graph

Leans on · 4Leaned on by · 1Acti9 Isobar UK catalogue — derived from, publishedActi9 Isobar UK cataloguederived fromActi9 low voltage catalogue — derived from, publishedActi9 low voltage cataloguederived fromActi9 iC40 catalogue — derived from, publishedActi9 iC40 cataloguederived fromiC60 tripping bands and FAQ — derived from, publishediC60 tripping bands andFAQderived fromDevice bands and hot upstream — used to derive, estimatedDevice bands and hotupstreamused to deriveActi9 devices Leans on · 4Leaned on by · 1Acti9 Isobar UK catalogue — derived from, publishedActi9 Isobar UKcataloguederived fromActi9 low voltage catalogue — derived from, publishedActi9 low voltagecataloguederived fromActi9 iC40 catalogue — derived from, publishedActi9 iC40cataloguederived fromiC60 tripping bands and FAQ — derived from, publishediC60 trippingbands and FAQderived fromDevice bands and hot upstream — used to derive, estimatedDevice bands andhot upstreamused to deriveActi9 devices Leans on · 4Leaned on by · 1Acti9 Isobar UK catalogue — derived from, publishedActi9 Isobar UKcataloguederived fromActi9 low voltage catalogue — derived from, publishedActi9 lowvoltagecataloguederived fromActi9 iC40 catalogue — derived from, publishedActi9 iC40cataloguederived fromiC60 tripping bands and FAQ — derived from, publishediC60 trippingbands and FAQderived fromDevice bands and hot upstream — used to derive, estimatedDevice bandsand hotupstreamused to deriveActi9 devices

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

Retained data

The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.

Read live through tools/selectivity/library/index.js · family. Catalogue rows, cells and curve coordinates are not reproduced.

How the calculator uses it

What the study keeps

Acti9 MCB, RCBO, PoN RCBO and Active frames, performances, ratings and residual settings. Published iC60 MCB bands are kept separately from generic envelopes.

The two File menu routes use iC60H devices. resolve() retains the exact frame and curve for table matching and supplies residual functions only where the selected device has them. See Acti9 Isobar UK catalogue, Acti9 low voltage catalogue, Acti9 iC40 catalogue, iC60 tripping bands and FAQ.

VERIFY

Do not transfer the iC60 MCB thermal band to every RCBO. Other modular thermal edges may be illustrative or published only at anchors.

Worked through on DNO-fed route

PairBS 88-3 100 A fuse → ComPacT NSXm F TM100D
Fault level at downstream board16 kA
Phase verdictNot selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published).
Phase statusfail
VERIFY from this runUpstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY).
PairComPacT NSXm F TM100D → Acti9 iC60H B16
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.