Table we keep · Selectivity Study
Acti9 devices
estimatedsel.table.acti9-devices
The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
Retained data
The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
Read live through tools/selectivity/library/index.js · family. Catalogue rows, cells and curve coordinates are not reproduced.
How the calculator uses it
What the study keeps
Acti9 MCB, RCBO, PoN RCBO and Active frames, performances, ratings and residual settings. Published iC60 MCB bands are kept separately from generic envelopes.
The two File menu routes use iC60H devices. resolve() retains the exact frame and curve for table matching and supplies residual functions only where the selected device has them. See Acti9 Isobar UK catalogue, Acti9 low voltage catalogue, Acti9 iC40 catalogue, iC60 tripping bands and FAQ.
VERIFY
Do not transfer the iC60 MCB thermal band to every RCBO. Other modular thermal edges may be illustrative or published only at anchors.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.