Document · Selectivity Study

Acti9 low voltage catalogue

published

sel.doc.ca909006e

iC60N/L and iCV40-family RCBO frame data.

Local graph

Leans on · 0Leaned on by · 1NothingActi9 devices — used to derive, estimatedActi9 devicesused to deriveActi9 low voltagecatalogue Leans on · 0Leaned on by · 1NothingActi9 devices — used to derive, estimatedActi9 devicesused to deriveActi9 lowvoltagecatalogue Leans on · 0Leaned on by · 1NothingActi9 devices — used to derive, estimatedActi9 devicesused to deriveActi9 low voltage catalogue

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The original document

Publisher
Schneider Electric
Title
CA909006E — Acti9 low voltage catalogue
Edition
07/2019
Where in it
22, 28, 48, 50, 252–257
Do we hold it
Owner’s local copy; not distributed
May it be reproduced here
In small extracts, quoted with acknowledgement. The document is the authority.

Schneider document download ↗ We are not the source of record.

What the document says

iC60N/L and iCV40-family RCBO frame data. See the original at 22, 28, 48, 50, 252–257; no extract is reproduced on this page.

How the calculator uses it

What the study keeps

The study retains the portions needed by Acti9 devices. Each retained dataset or method keeps the original source locator.

The source is used for iC60N/L and iCV40-family RCBO frame data. Follow the connected nodes to see the actual retained data and method, then the live worked result below.

VERIFY

Check 07/2019 against the actual device and current manufacturer instructions. Source pages: 22, 28, 48, 50, 252–257.

Worked through on DNO-fed route

PairBS 88-3 100 A fuse → ComPacT NSXm F TM100D
Fault level at downstream board16 kA
Phase verdictNot selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published).
Phase statusfail
VERIFY from this runUpstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY).
PairComPacT NSXm F TM100D → Acti9 iC60H B16
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.