Rule · Selectivity Study
iC60 drawn feet
publishedsel.rule.drawn-feet
C, D and K have distinct drawn feet beyond the earlier magnetic band. Join each foot to the faster I²t extension; do not treat the missing common edge as published.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
What the study keeps
The selected curve’s published foot and the end of the common lower edge are retained separately.
mcbBand() joins the foot to the faster I²t extension after the common edge ends. This avoids treating a missing shared segment as a published slow edge. See iC60 tripping bands.
VERIFY
Use the correct C, D or K foot. A common thermal envelope is not interchangeable with each curve’s complete published lower boundary.
Worked through on DNO-fed route
| Pair | BS 88-3 100 A fuse → ComPacT NSXm F TM100D |
|---|---|
| Fault level at downstream board | 16 kA |
| Phase verdict | Not selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published). |
| Phase status | fail |
| VERIFY from this run | Upstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY). |
| Pair | ComPacT NSXm F TM100D → Acti9 iC60H B16 |
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity. |
| Phase status | pass |