Rule · Selectivity Study

iC60 drawn feet

published

sel.rule.drawn-feet

C, D and K have distinct drawn feet beyond the earlier magnetic band. Join each foot to the faster I²t extension; do not treat the missing common edge as published.

Local graph

Leans on · 1Leaned on by · 1iC60 tripping bands — derived from, publishediC60 tripping bandsderived fromPhase faults — used to derive, estimatedPhase faultsused to deriveiC60 drawn feet Leans on · 1Leaned on by · 1iC60 tripping bands — derived from, publishediC60 trippingbandsderived fromPhase faults — used to derive, estimatedPhase faultsused to deriveiC60 drawn feet Leans on · 1Leaned on by · 1iC60 tripping bands — derived from, publishediC60 trippingbandsderived fromPhase faults — used to derive, estimatedPhase faultsused to deriveiC60 drawn feet

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

How the calculator uses it

What the study keeps

The selected curve’s published foot and the end of the common lower edge are retained separately.

mcbBand() joins the foot to the faster I²t extension after the common edge ends. This avoids treating a missing shared segment as a published slow edge. See iC60 tripping bands.

VERIFY

Use the correct C, D or K foot. A common thermal envelope is not interchangeable with each curve’s complete published lower boundary.

Worked through on DNO-fed route

PairBS 88-3 100 A fuse → ComPacT NSXm F TM100D
Fault level at downstream board16 kA
Phase verdictNot selective from 580 A to 1.45 kA: the bands overlap. Probably from 126 A (an edge that is not published).
Phase statusfail
VERIFY from this runUpstream fuse fastest edge: IEC 60269-1 gG gates (VERIFY).
PairComPacT NSXm F TM100D → Acti9 iC60H B16
Fault level at downstream board4.2 kA
Phase verdictTotal selectivity (Schneider p. A-62: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.