Table we keep · Selectivity Study
NS, NT and NW devices
estimatedsel.table.legacy-devices
The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
Retained data
The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.
Read live through tools/selectivity/library/index.js · family. Catalogue rows, cells and curve coordinates are not reproduced.
How the calculator uses it
What the study keeps
NS, NT and NW frames and MicroLogic A/E settings from their catalogues and user guides, with the chosen timing basis.
The supplemental NS and NT examples exercise these resolved bands. NS can match guide entries; NT/NW have no tested instantaneous-zone basis in the current guide. See ComPact NS documents, MasterPact NT and NW documents.
VERIFY
The source timings disagree at the shortest long-time setting and instantaneous break time. The study follows the catalogue; verify against the fitted unit.
Worked through on an NT incomer
| Pair | Masterpact NT06 H1 MicroLogic 5.0 A/E 630 A → Acti9 iC60H B16 |
|---|---|
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Selective up to the 4.2 kA fault level: the bands do not overlap. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.