Document · Selectivity Study

MasterPact NT and NW documents

published

sel.doc.ntnw-documents

Legacy frames and trip units; no tested instantaneous pair basis in the current guide.

Local graph

Leans on · 0Leaned on by · 1NothingNS, NT and NW devices — used to derive, estimatedNS, NT and NW devicesused to deriveMasterPact NT andNW documents Leans on · 0Leaned on by · 1NothingNS, NT and NW devices — used to derive, estimatedNS, NT and NWdevicesused to deriveMasterPact NTand NWdocuments Leans on · 0Leaned on by · 1NothingNS, NT and NW devices — used to derive, estimatedNS, NT and NWdevicesused to deriveMasterPact NT and NWdocuments

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The original document

Publisher
Schneider Electric
Title
LVPED208008EN; 04443724AA — MasterPact NT and NW documents
Edition
2020; 03/2012
Where in it
catalogue A-5/A-7; MicroLogic A/E settings
Do we hold it
Owner’s local copy; not distributed
May it be reproduced here
In small extracts, quoted with acknowledgement. The document is the authority.

Schneider document download ↗ We are not the source of record.

What the document says

Legacy frames and trip units; no tested instantaneous pair basis in the current guide. See the original at catalogue A-5/A-7; MicroLogic A/E settings; no extract is reproduced on this page.

How the calculator uses it

What the study keeps

The study retains the portions needed by NS, NT and NW devices. Each retained dataset or method keeps the original source locator.

The source is used for legacy frames and trip units; no tested instantaneous pair basis in the current guide. Follow the connected nodes to see the actual retained data and method, then the live worked result below.

VERIFY

Check 2020; 03/2012 against the actual device and current manufacturer instructions. Source pages: catalogue A-5/A-7; MicroLogic A/E settings.

Worked through on an NT incomer

PairMasterpact NT06 H1 MicroLogic 5.0 A/E 630 A → Acti9 iC60H B16
Fault level at downstream board4.2 kA
Phase verdictSelective up to the 4.2 kA fault level: the bands do not overlap.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.