Document · Selectivity Study
ComPact NS documents
publishedsel.doc.ns-documents
NS frames and MicroLogic A/E; catalogue timing wins where guides disagree.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The original document
- Publisher
- Schneider Electric
- Title
- LVPED211021EN; DOCA0217EN; DOCA0218EN — ComPact NS documents
- Edition
- 2020; user guides 01/2022
- Where in it
- catalogue A-3, A-9–A-13; DOCA0217EN p.21
- Do we hold it
- Owner’s local copy; not distributed
- May it be reproduced here
- In small extracts, quoted with acknowledgement. The document is the authority.
Schneider document download ↗ We are not the source of record.
What the document says
NS frames and MicroLogic A/E; catalogue timing wins where guides disagree. See the original at catalogue A-3, A-9–A-13; DOCA0217EN p.21; no extract is reproduced on this page.
How the calculator uses it
What the study keeps
The study retains the portions needed by NS, NT and NW devices. Each retained dataset or method keeps the original source locator.
The source is used for nS frames and MicroLogic A/E; catalogue timing wins where guides disagree. Follow the connected nodes to see the actual retained data and method, then the live worked result below.
VERIFY
Check 2020; user guides 01/2022 against the actual device and current manufacturer instructions. Source pages: catalogue A-3, A-9–A-13; DOCA0217EN p.21.
Worked through on an NS incomer
| Pair | ComPacT NS630bN MicroLogic 5.0 A/E 630 A → Acti9 iC60H B16 |
|---|---|
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Selective up to the 4.2 kA fault level: the bands do not overlap. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.