Table we keep · Selectivity Study

MTZ devices

estimated

sel.table.mtz-devices

The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.

Local graph

Leans on · 3Leaned on by · 1MTZ with MicroLogic X catalogue — derived from, publishedMTZ with MicroLogic Xcataloguederived fromMTZ Active catalogue — derived from, publishedMTZ Active cataloguederived fromMicroLogic X user guide — derived from, publishedMicroLogic X user guidederived fromDevice bands and hot upstream — used to derive, estimatedDevice bands and hotupstreamused to deriveMTZ devices Leans on · 3Leaned on by · 1MTZ with MicroLogic X catalogue — derived from, publishedMTZ withMicroLogic Xcataloguederived fromMTZ Active catalogue — derived from, publishedMTZ Activecataloguederived fromMicroLogic X user guide — derived from, publishedMicroLogic X userguidederived fromDevice bands and hot upstream — used to derive, estimatedDevice bands andhot upstreamused to deriveMTZ devices Leans on · 3Leaned on by · 1MTZ with MicroLogic X catalogue — derived from, publishedMTZ withMicroLogic Xcataloguederived fromMTZ Active catalogue — derived from, publishedMTZ Activecataloguederived fromMicroLogic X user guide — derived from, publishedMicroLogic Xuser guidederived fromDevice bands and hot upstream — used to derive, estimatedDevice bandsand hotupstreamused to deriveMTZ devices

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

Retained data

The device library resolves the selected frame, rating and real dial settings into a band with source pointers. Missing published edges remain indicative.

Read live through tools/selectivity/library/index.js · family. Catalogue rows, cells and curve coordinates are not reproduced.

How the calculator uses it

What the study keeps

MTZ frames and sensors, MicroLogic X and Active trip functions, short-time modes and breaking capacities.

The transformer example resolves MicroLogic X long-time, short-time, instantaneous and ground-fault functions. An Active device can use curves but has no tested pair entry in the guide. See MTZ with MicroLogic X catalogue, MTZ Active catalogue, MicroLogic X user guide.

VERIFY

Check ZSI state and Standard/Fast mode. An open MicroLogic X ZSI input can shorten the delay; a dial setting alone does not establish the holding time.

Worked through on Transformer-fed route

PairMasterPacT MTZ2 16 H1 MicroLogic 6.0 X 1600 A → ComPacT NSX250N MicroLogic 5.2 E 250 A
Fault level at downstream board38 kA
Phase verdictTotal selectivity (Schneider p. A-88: T), up to the downstream device's breaking capacity.
Phase statuspass
Earth verdictEarth faults: selective on the curves up to 21.6 kA; above that both can trip instantaneously and the guide's tables cover phase faults only (p. A-75 note), so it is indicative.
PairComPacT NSX250N MicroLogic 5.2 E 250 A → Acti9 iC60H C32
Fault level at downstream board9.2 kA
Phase verdictTotal selectivity (Schneider p. A-68: T), up to the downstream device's breaking capacity.
Phase statuspass