Document · Selectivity Study
MTZ with MicroLogic X catalogue
publishedsel.doc.lvped216026en
MTZ frames, sensors, breaking capacities and MicroLogic X settings.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The original document
- Publisher
- Schneider Electric
- Title
- LVPED216026EN — MTZ with MicroLogic X catalogue
- Edition
- January 2025
- Where in it
- A-6/A-7; B-8/B-9
- Do we hold it
- Owner’s local copy; not distributed
- May it be reproduced here
- In small extracts, quoted with acknowledgement. The document is the authority.
Schneider document download ↗ We are not the source of record.
What the document says
MTZ frames, sensors, breaking capacities and MicroLogic X settings. See the original at A-6/A-7; B-8/B-9; no extract is reproduced on this page.
How the calculator uses it
What the study keeps
The study retains the portions needed by MTZ devices. Each retained dataset or method keeps the original source locator.
The source is used for mTZ frames, sensors, breaking capacities and MicroLogic X settings. Follow the connected nodes to see the actual retained data and method, then the live worked result below.
VERIFY
Check January 2025 against the actual device and current manufacturer instructions. Source pages: A-6/A-7; B-8/B-9.
Worked through on Transformer-fed route
| Pair | MasterPacT MTZ2 16 H1 MicroLogic 6.0 X 1600 A → ComPacT NSX250N MicroLogic 5.2 E 250 A |
|---|---|
| Fault level at downstream board | 38 kA |
| Phase verdict | Total selectivity (Schneider p. A-88: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
| Earth verdict | Earth faults: selective on the curves up to 21.6 kA; above that both can trip instantaneously and the guide's tables cover phase faults only (p. A-75 note), so it is indicative. |
| Pair | ComPacT NSX250N MicroLogic 5.2 E 250 A → Acti9 iC60H C32 |
| Fault level at downstream board | 9.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-68: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.