Document · Selectivity Study

MicroLogic X user guide

published

sel.doc.doca0102en

Long-time, short-time, instantaneous and ground-fault settings and tolerances.

Local graph

Leans on · 0Leaned on by · 1NothingMTZ devices — used to derive, estimatedMTZ devicesused to deriveMicroLogic X userguide Leans on · 0Leaned on by · 1NothingMTZ devices — used to derive, estimatedMTZ devicesused to deriveMicroLogic Xuser guide Leans on · 0Leaned on by · 1NothingMTZ devices — used to derive, estimatedMTZ devicesused to deriveMicroLogic X user guide

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The original document

Publisher
Schneider Electric
Title
DOCA0102EN — MicroLogic X user guide
Edition
12
Where in it
105–118
Do we hold it
Owner’s local copy; not distributed
May it be reproduced here
In small extracts, quoted with acknowledgement. The document is the authority.

Schneider document download ↗ We are not the source of record.

What the document says

Long-time, short-time, instantaneous and ground-fault settings and tolerances. See the original at 105–118; no extract is reproduced on this page.

How the calculator uses it

What the study keeps

The study retains the portions needed by MTZ devices. Each retained dataset or method keeps the original source locator.

The source is used for long-time, short-time, instantaneous and ground-fault settings and tolerances. Follow the connected nodes to see the actual retained data and method, then the live worked result below.

VERIFY

Check 12 against the actual device and current manufacturer instructions. Source pages: 105–118.

Worked through on Transformer-fed route

PairMasterPacT MTZ2 16 H1 MicroLogic 6.0 X 1600 A → ComPacT NSX250N MicroLogic 5.2 E 250 A
Fault level at downstream board38 kA
Phase verdictTotal selectivity (Schneider p. A-88: T), up to the downstream device's breaking capacity.
Phase statuspass
Earth verdictEarth faults: selective on the curves up to 21.6 kA; above that both can trip instantaneously and the guide's tables cover phase faults only (p. A-75 note), so it is indicative.
PairComPacT NSX250N MicroLogic 5.2 E 250 A → Acti9 iC60H C32
Fault level at downstream board9.2 kA
Phase verdictTotal selectivity (Schneider p. A-68: T), up to the downstream device's breaking capacity.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.