Document · Selectivity Study
MicroLogic X user guide
publishedsel.doc.doca0102en
Long-time, short-time, instantaneous and ground-fault settings and tolerances.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The original document
- Publisher
- Schneider Electric
- Title
- DOCA0102EN — MicroLogic X user guide
- Edition
- 12
- Where in it
- 105–118
- Do we hold it
- Owner’s local copy; not distributed
- May it be reproduced here
- In small extracts, quoted with acknowledgement. The document is the authority.
Schneider document download ↗ We are not the source of record.
What the document says
Long-time, short-time, instantaneous and ground-fault settings and tolerances. See the original at 105–118; no extract is reproduced on this page.
How the calculator uses it
What the study keeps
The study retains the portions needed by MTZ devices. Each retained dataset or method keeps the original source locator.
The source is used for long-time, short-time, instantaneous and ground-fault settings and tolerances. Follow the connected nodes to see the actual retained data and method, then the live worked result below.
VERIFY
Check 12 against the actual device and current manufacturer instructions. Source pages: 105–118.
Worked through on Transformer-fed route
| Pair | MasterPacT MTZ2 16 H1 MicroLogic 6.0 X 1600 A → ComPacT NSX250N MicroLogic 5.2 E 250 A |
|---|---|
| Fault level at downstream board | 38 kA |
| Phase verdict | Total selectivity (Schneider p. A-88: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
| Earth verdict | Earth faults: selective on the curves up to 21.6 kA; above that both can trip instantaneously and the guide's tables cover phase faults only (p. A-75 note), so it is indicative. |
| Pair | ComPacT NSX250N MicroLogic 5.2 E 250 A → Acti9 iC60H C32 |
| Fault level at downstream board | 9.2 kA |
| Phase verdict | Total selectivity (Schneider p. A-68: T), up to the downstream device's breaking capacity. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.