Document · Selectivity Study

MTZ Active catalogue

published

sel.doc.lvped225010en

Active frames and settings; this family is absent from the guide tables.

Local graph

Leans on · 0Leaned on by · 1NothingMTZ devices — used to derive, estimatedMTZ devicesused to deriveMTZ Active catalogue Leans on · 0Leaned on by · 1NothingMTZ devices — used to derive, estimatedMTZ devicesused to deriveMTZ Activecatalogue Leans on · 0Leaned on by · 1NothingMTZ devices — used to derive, estimatedMTZ devicesused to deriveMTZ Active catalogue

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The original document

Publisher
Schneider Electric
Title
LVPED225010EN — MTZ Active catalogue
Edition
September 2025
Where in it
A-6/A-7; B-9–B-11
Do we hold it
Owner’s local copy; not distributed
May it be reproduced here
In small extracts, quoted with acknowledgement. The document is the authority.

Schneider document download ↗ We are not the source of record.

What the document says

Active frames and settings; this family is absent from the guide tables. See the original at A-6/A-7; B-9–B-11; no extract is reproduced on this page.

How the calculator uses it

What the study keeps

The study retains the portions needed by MTZ devices. Each retained dataset or method keeps the original source locator.

The source is used for active frames and settings; this family is absent from the guide tables. Follow the connected nodes to see the actual retained data and method, then the live worked result below.

VERIFY

Check September 2025 against the actual device and current manufacturer instructions. Source pages: A-6/A-7; B-9–B-11.

Worked through on an MTZ Active incomer

PairMasterPacT MTZ1 06 H1 MicroLogic Active 5.0 630 A → Acti9 iC60H B16
Fault level at downstream board4.2 kA
Phase verdictSelective up to the 4.2 kA fault level: the bands do not overlap.
Phase statuspass

Computed by the calculator for this run when this page was generated — not typed.