Document · Selectivity Study
MTZ Active catalogue
publishedsel.doc.lvped225010en
Active frames and settings; this family is absent from the guide tables.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The original document
- Publisher
- Schneider Electric
- Title
- LVPED225010EN — MTZ Active catalogue
- Edition
- September 2025
- Where in it
- A-6/A-7; B-9–B-11
- Do we hold it
- Owner’s local copy; not distributed
- May it be reproduced here
- In small extracts, quoted with acknowledgement. The document is the authority.
Schneider document download ↗ We are not the source of record.
What the document says
Active frames and settings; this family is absent from the guide tables. See the original at A-6/A-7; B-9–B-11; no extract is reproduced on this page.
How the calculator uses it
What the study keeps
The study retains the portions needed by MTZ devices. Each retained dataset or method keeps the original source locator.
The source is used for active frames and settings; this family is absent from the guide tables. Follow the connected nodes to see the actual retained data and method, then the live worked result below.
VERIFY
Check September 2025 against the actual device and current manufacturer instructions. Source pages: A-6/A-7; B-9–B-11.
Worked through on an MTZ Active incomer
| Pair | MasterPacT MTZ1 06 H1 MicroLogic Active 5.0 630 A → Acti9 iC60H B16 |
|---|---|
| Fault level at downstream board | 4.2 kA |
| Phase verdict | Selective up to the 4.2 kA fault level: the bands do not overlap. |
| Phase status | pass |
Computed by the calculator for this run when this page was generated — not typed.