Reference · CMS calculator
How the containment calculator works
Left to right: the documents it reads, the tables it keeps from them, the rules that shape them, the checks that run, and the verdict. Every box opens the page that says where it came from and how it is used.
Solid: what 4 × 4c 95mm² on a 600 mm wide ladder, cleated, with a fault current, leans on.
Solid: what a trunking run of 12 × 1c 6mm², 6 × 1c 10mm², 4 × 1c 16mm² leans on.
Everything in the CMS section, whether a run touches it or not.
leaned on by the run shownin the library, not used by it
Documents
- Swifts cable ladder catalogue 2025 — rungs — How far apart the rungs are, and the section of the standard rung with the slots punched in it — the rung every cleat bolts to.
- Swifts cable ladder catalogue 2025 — Table 6 — The ladder maker’s own table of minimum bending radii, by type of cable.
- Swifts IEC ladder model files — The manufacturer’s own model data: each family’s outside and inside height, and the inside width of every size.
- Swifts cable ladder product pages — The usable cross-section the maker publishes for each ladder straight — what a grouped run is sized against.
- Cablofil wire basket product pages — The useful cross-section the maker publishes for the shallow wire baskets.
- Swifts cable tray technical guide — Which tray depths the maker makes at which width.
- Cleat catalogue 001816-3 — The two-bolt and single-bolt nylon cleat ranges: which cable each fits, how wide it is, where its bolts go.
- 2A clamps — data sheet DS17E — The aluminium two-hole cleat range, its dimensions and its short-circuit tests.
- 2F+ two hole clamp — data sheet DS20E — The current sheet for the two-bolt nylon clamp: its heights and bolts, and its short-circuit tests with their conditions.
- 1F clamps — data sheet DS33E — The single-bolt clamp’s short-circuit test — the LSF version tested, the standard one not.
- Short-circuit test reports — The tests behind the rated withstand the calculator proposes for a cleat range — proposed, never entered for you.
- Installation — Cable Bending Radii — The cable maker’s minimum bending radii — and its advice to bend larger wherever possible.
- BICON 419CE brass CW glands — How far a gland stands outside the gland plate, by cable diameter — a length example for the drop.
- Draka / Prysmian and Amtech cable catalogues — Where every cable’s outside diameter, area, weight and published bending radius comes from.
- Adaptaflex data sheet — cable carrying capacity — The flexible conduit maker’s own fill rule, and the inside area of every size of its two ranges. Linked, never reproduced.
- Adaptaflex catalogues 2022 — The inside diameter of every size of the maker’s flexible conduit ranges: where the steel SP sizes and the plastic 48 mm come from. Linked, never reproduced.
- TLC Direct oval conduit pages — The inside width and height of three sizes of oval conduit — a distributor’s figures, because the maker publishes only the outside.
- Sparkline’s project cable data — Insulation thicknesses taken from project cable data — project practice, not a published standard.
- Cable cleat calculation workbook — Sparkline’s workbook the cleat force method, its constants and the core spacing were transcribed from.
- CMS capacity workbook — Sparkline’s workbook every cable and containment table was generated from.
- IET Guidance Note 1, Appendix A — Where the space factors, the trunking capacities and the conduit factors come from. Cited, never reproduced.
- BS 7671:2018+A4:2026 — Why the cleat check exists, and the regulations the design checks point to. Cited, never reproduced.
- BS EN IEC 61914 — cable cleats — The standard cleats are tested to, and the one the workbook’s force method is attributed to. Cited, never reproduced.
- BS 5467 / BS 6724 — The cable standards the published insulation thicknesses come from. Named only: not held, never reproduced.
Tables we keep
- Cable catalogue — Every cable the schedule can pick, with the dimensions the sizing, the bend check and the cleat check read.
- Trunking net internal areas — The cross-section each trunking size offers before the space factor is applied.
- Duct bore areas — The bore of each duct, worked out as a circle from its internal diameter.
- Ladder widths and usable sections — Each ladder size’s inside width — what a laid run is measured against — and the usable section a grouped run is sized on.
- Tray sizes — The tray widths and depths, and which of them the maker actually makes.
- Wire basket sections — The wire basket sizes: width × height from the workbook, and the useful section the maker publishes for the shallow ones.
- Conduit and cable factors — The factors the conduit method adds up: one per cable, one per conduit, for a run’s length and bends.
- Flexible conduit inside areas — The inside area of every size of the maker’s flexible conduit ranges the calculator offers — what its fill rule is a share of.
- Oval conduit inside sizes — The inside width and height of each oval size, and the inside area worked out from them as a rectangle with round ends.
- Cleat catalogue — Every cleat the calculator can propose or be given, with the dimensions the drawings and the arrangement read.
- Cleat short-circuit declarations — What each cleat range has survived, and under which conditions — a bound on the duty, not a spacing.
- Ladder bend fittings — The bend fittings each ladder family is made in — which radius a turn can take off the shelf.
- Gland lengths — How far a gland stands outside the plate, which the drop adds to the height a cable needs.
- Insulation thickness — The insulation on one conductor, by size — it sets how far apart the cores sit, which sets the force between them.
- Formation constants K — The constant the force law takes for each way the conductors can lie.
- Rung and slot geometry — The rung every cable and cleat stands on, and the slots its bolts go through.
- Ladder rail heights — How deep each ladder family’s rails are, and how far up them the rung sits.
Rules
- Space factor — How much of a closed section the cables may fill — the rest is the room that lets them be drawn in and stay cool.
- Flexible conduit fill — How much of a flexible conduit’s cross-section the cables may take — the maker’s rule, for three or more cables: of the inside area on PA and SP, of ABB’s fill value on SPL.
- Oval conduit fill — How much of an oval conduit’s inside area the cables may take. No maker or standard publishes a figure, so this one is the calculator’s own, changeable per run.
- Future spare — The part of every size kept clear for cables added later — Sparkline’s default, none on conduit, changeable per run.
- Layout spacing — How much width each cable takes when laid in a single layer, touching or spaced.
- The no-clash rule for cleats — How close two cleats, or a cleat and a cable, may stand across a rung — the rule every arrangement and every drag obeys.
- Bending radius basis — Which minimum radius a cable is bent at: its catalogue figure, or a multiple of its diameter.
- Allowance over the minimum radius — An optional margin over the minimum radius — derived, because the cable maker publishes no figure for LV cable.
- The force on a cleat — The force a fault puts on each cleat, and from it the longest gap a cleat can hold — rounded down to whole rungs.
- Power cables only — Only cables that can carry the run’s fault current are force-checked; a cable of more cores is a control cable.
- The drop, measured from the rung top — Where the height a cable needs on its way into a switchboard is measured from, and what it is made of.
- Segregation bands — Which cables may share a containment: power, data and fire alarm, by voltage band.
Checks
- Fill by area — The sizing check for a closed section, or a pile: the cables’ areas against the usable area — trunking, duct, flexible and oval conduit, a grouped open run.
- Fill by width — The sizing check for a single layer: the width the cables and their spacing take against the usable width.
- Conduit factors — The conduit check: the cables’ factors against the conduit’s, for its length and bends.
- Bends — Whether every cable can turn inside the containment’s bends, and which fitting that needs.
- Cable weight — The weight the cables put on the containment, per metre, for the supports to be checked against.
- Segregation — Whether cables of different bands share the containment without a barrier.
- Cable cleat check — The maximum spacing of cleats for the run’s fault current, and whether the run as laid is inside it.
- Cleat bolts in the rung slots — Whether each cleat’s bolts land in the rung’s slots, or on the metal between them.
- The drop into a switchboard — The height the cables need between the ladder and a board’s gland plate.