Table we keep · CMS calculator
Gland lengths
estimatedcms.table.glands
One maker's gland range, as a distributor lists it: for each size, the cables it takes and how far it stands outside the gland plate.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The table we actually use
| Part | Size | Cable Ø mm | Thread | Outside the plate mm | State |
|---|---|---|---|---|---|
| 419CE-52 | 20S | 8–15.8 | M20×1.5 | 56 | ◐ estimated: a distributor’s listing, not the maker’s data sheet — a length example, not a gland selection |
| 419CE-53 | 20 | 11.7–20.8 | M20×1.5 | 56 | ◐ estimated: a distributor’s listing, not the maker’s data sheet — a length example, not a gland selection |
| 419CE-55 | 25 | 17–27.2 | M25×1.5 | 63 | ◐ estimated: a distributor’s listing, not the maker’s data sheet — a length example, not a gland selection |
| 419CE-56 | 32 | 23.5–33.5 | M32×1.5 | 73 | ◐ estimated: a distributor’s listing, not the maker’s data sheet — a length example, not a gland selection |
| 419CE-57 | 40 | 29–39.9 | M40×1.5 | 77 | ◐ estimated: a distributor’s listing, not the maker’s data sheet — a length example, not a gland selection |
| 419CE-59 | 50 | 39.5–52.6 | M50×1.5 | 84 | ◐ estimated: a distributor’s listing, not the maker’s data sheet — a length example, not a gland selection |
| 419CE-61 | 63 | 51.3–65.3 | M63×1.5 | 84 | ◐ estimated: a distributor’s listing, not the maker’s data sheet — a length example, not a gland selection |
| 419CE-63 | 75 | 62.5–78 | M75×1.5 | 94 | ◐ estimated: a distributor’s listing, not the maker’s data sheet — a length example, not a gland selection |
| 419CE-64 | 85 | 68–88 | M85×2.0 | 125 | ◐ estimated: a distributor’s listing, not the maker’s data sheet — a length example, not a gland selection |
| 419CE-65 | 90 | 79–90 | M90×2.0 | 152 | ◐ estimated: a distributor’s listing, not the maker’s data sheet — a length example, not a gland selection |
| 419CE-66 | 100 | 89–99 | M100×2.0 | 152 | ◐ estimated: a distributor’s listing, not the maker’s data sheet — a length example, not a gland selection |
| 419CE-67 | 110 | 99.5–112.5 | M110×2.0 | 152 | ◐ estimated: a distributor’s listing, not the maker’s data sheet — a length example, not a gland selection |
12 rows · 12 marked estimated (hover the mark for why) · read live from tools/cms-calc/glands.js GLAND_RANGES
How the calculator uses it
The drop adds the gland's length outside the plate to the height a cable needs on its way into a board. A gap in the listing is reported, never rounded away.
Watch for
The pick is by overall diameter alone — a length example, not a gland selection. Type the length of the gland you fit if you have it.
Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung, the ladder above the board, 640 mm to the gland plate
| The cable that needs the most | A1 · Ø 41.7 mm |
|---|---|
| Its radius, as the basis chosen | 334 mm to the cable axis |
| The turn, to its inner surface | 313 mm |
| The straight before the gland | 20 mm |
| The gland outside the plate | 84 mm (419CE-59) |
| Needed, from the rung top | 417 mm |
| Verdict | OK — 223 mm in hand |
Computed by the calculator for this run when this page was generated — not typed.
VERIFY before issue
Transcribed from a distributor listing, not from the Prysmian data sheet. Check every figure against the manufacturer before issuing a sheet that relies on it. The under-armour diameter (column A) is not checked by the tool.
glands.note — the calculator’s own words, not a copy