The drop into a switchboard

estimated

cms.check.drop

The height the cables need between the ladder and a board's gland plate, against the height you have.

Local graph

Leans on · 7Leaned on by · 1Cable catalogue — fed by, estimatedCable cataloguefed byGland lengths — fed by, estimatedGland lengthsfed byRung and slot geometry — fed by · the rung top, estimatedRung and slot geometryfed by · the rung topLadder rail heights — fed by, publishedLadder rail heightsfed byBending radius basis — fed by, a choiceBending radius basisfed byAllowance over the minimum radius — fed by, estimatedAllowance over theminimum radiusfed byThe drop, measured from the rung top — fed by, a choiceThe drop, measured fromthe rung topfed byCable Containment Capacity Calculator — feeds, estimatedCable ContainmentCapacity CalculatorfeedsThe drop into aswitchboard Leans on · 7Leaned on by · 1Cable catalogue — fed by, estimatedCable cataloguefed byGland lengths — fed by, estimatedGland lengthsfed byRung and slot geometry — fed by · the rung top, estimatedRung and slotgeometryfed by · the rung topLadder rail heights — fed by, publishedLadder rail heightsfed byBending radius basis — fed by, a choiceBending radiusbasisfed byAllowance over the minimum radius — fed by, estimatedAllowance overthe minimumradiusfed byThe drop, measured from the rung top — fed by, a choiceThe drop,measured fromthe rung topfed byCable Containment Capacity Calculator — feeds, estimatedCableContainmentCapacityCalculatorfeedsThe drop into aswitchboard Leans on · 7Leaned on by · 1Cable catalogue — fed by, estimatedCablecataloguefed byGland lengths — fed by, estimatedGland lengthsfed byRung and slot geometry — fed by · the rung top, estimatedRung and slotgeometryfed by · the rungtopLadder rail heights — fed by, publishedLadder railheightsfed byBending radius basis — fed by, a choiceBending radiusbasisfed byAllowance over the minimum radius — fed by, estimatedAllowance overthe minimumradiusfed byThe drop, measured from the rung top — fed by, a choiceThe drop,measured fromthe rung topfed byCable Containment Capacity Calculator — feeds, estimatedCableContainmentCapacityCalculatorfeedsThe drop into a switchboard

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

How the calculator uses it

It is worked out for every cable from its radius, the straight before the gland and the gland's length; the cable that needs the most governs. Advisory — it does not change the containment's verdict.

Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung, the ladder above the board, 640 mm to the gland plate

The cable that needs the mostA1 · Ø 41.7 mm
Its radius, as the basis chosen334 mm to the cable axis
The turn, to its inner surface313 mm
The straight before the gland20 mm
The gland outside the plate84 mm (419CE-59)
Needed, from the rung top417 mm
VerdictOK — 223 mm in hand

Computed by the calculator for this run when this page was generated — not typed.

VERIFY before issue

Transcribed from a distributor listing, not from the Prysmian data sheet. Check every figure against the manufacturer before issuing a sheet that relies on it. The under-armour diameter (column A) is not checked by the tool.

glands.note — the calculator’s own words, not a copy