Rule · CMS calculator
Bending radius basis
a choicecms.rule.bendBasis
Which minimum radius a cable is bent at: the figure its catalogue publishes, or a multiple of its diameter. Eight times the diameter is the default — Sparkline's decision — and a row in the schedule can carry its own.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The table we actually use
| Basis | × O.D. | State | |
|---|---|---|---|
| Cable catalogue figure | — | — | |
| 6 × O.D. | 6 | — | |
| 8 × O.D. | 8 | default | |
| Typed multiple of O.D. | — | — |
4 rows
How the calculator uses it
The bend check and the drop read every cable's radius from one resolver, so the two can never give one cable two radii. Wherever the catalogue's own figure differs, it is printed beside the one in use.
Watch for
For armoured cable, eight times agrees with both the cable maker and the ladder maker. For unarmoured cable no document asks for it, and the calculator says so wherever it shows a figure it produced.
Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung, the ladder above the board, 640 mm to the gland plate
| The cable that needs the most | A1 · Ø 41.7 mm |
|---|---|
| Its radius, as the basis chosen | 334 mm to the cable axis |
| The turn, to its inner surface | 313 mm |
| The straight before the gland | 20 mm |
| The gland outside the plate | 84 mm (419CE-59) |
| Needed, from the rung top | 417 mm |
| Verdict | OK — 223 mm in hand |
Computed by the calculator for this run when this page was generated — not typed.