Check · CMS calculator

Bends

published

cms.check.bends

Whether every cable on the run can turn inside the containment's bends, and which fitting that needs.

Local graph

Leans on · 4Leaned on by · 1Cable catalogue — fed by, estimatedCable cataloguefed byLadder bend fittings — fed by, publishedLadder bend fittingsfed byBending radius basis — fed by, a choiceBending radius basisfed byAllowance over the minimum radius — fed by, estimatedAllowance over theminimum radiusfed byCable Containment Capacity Calculator — feeds, estimatedCable ContainmentCapacity CalculatorfeedsBends Leans on · 4Leaned on by · 1Cable catalogue — fed by, estimatedCable cataloguefed byLadder bend fittings — fed by, publishedLadder bendfittingsfed byBending radius basis — fed by, a choiceBending radiusbasisfed byAllowance over the minimum radius — fed by, estimatedAllowance overthe minimumradiusfed byCable Containment Capacity Calculator — feeds, estimatedCableContainmentCapacityCalculatorfeedsBends Leans on · 4Leaned on by · 1Cable catalogue — fed by, estimatedCablecataloguefed byLadder bend fittings — fed by, publishedLadder bendfittingsfed byBending radius basis — fed by, a choiceBending radiusbasisfed byAllowance over the minimum radius — fed by, estimatedAllowance overthe minimumradiusfed byCable Containment Capacity Calculator — feeds, estimatedCableContainmentCapacityCalculatorfeedsBends

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

How the calculator uses it

Each cable's radius, on its basis, is measured against the fitting — the cable on the inside of the turn has the least room. It names a stocked fitting where one will do, and a made-to-order one where not. Advisory: it does not change the containment's verdict.

VERIFY before issue

The published radius is struck at the INNER edge of the ladder, derived twice and never assumed. First: the catalogue’s own `C` (centre-line length to the intersection) follows (R + W/2)·tan(θ/2) + 80 across every flat-bend row — the +W/2 term is the width’s contribution to the centreline, which it could not have if R were already the centreline. Second: `i`, which the catalogue defines in its own words as "measurement across the inner curve", is 2R·sin(θ/2) — the chord of an arc of radius R — across all 360 riser rows to 0.5 mm.

fittings.datum — the calculator’s own words, not a copy

Both riser types are modelled with the governing cable at the fitting’s INNER radius (Sparkline’s rule). On an outside riser the cables lie on the convex face, which the geometry above puts at R + the rail depth — so an outside riser may be more generous than reported by up to 100 mm (Topaz), 125 mm (Sapphire) or 150 mm (Emerald). It is never reported as better than it is.

fittings.outsideRiserConservative — the calculator’s own words, not a copy