Table we keep · CMS calculator
Ladder bend fittings
publishedcms.table.fittingRadii
The bend fittings each Swifts ladder family is made in: the radii, the angles, and the radii held in stock.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The table we actually use
| Family | Rail mm | Inside height mm | Radii mm | Stocked radii mm | Angles | State |
|---|---|---|---|---|---|---|
| Swifts Topaz (medium duty) | 100 | 69 | 300 / 450 / 600 / 750 / 900 | 300 / 600 | 30° / 45° / 60° / 90° | |
| Swifts Sapphire (heavy duty) | 125 | 94 | 300 / 450 / 600 / 750 / 900 | 300 / 600 | 30° / 45° / 60° / 90° | |
| Swifts Emerald (extra heavy duty) | 150 | 119 | 300 / 450 / 600 / 750 / 900 | 300 / 600 | 30° / 45° / 60° / 90° |
3 rows · read live from tools/cms-calc/fittings.js FITTING_FAMILIES
How the calculator uses it
The bend check finds the smallest fitting radius that every cable on the run can turn on, and names a made-to-order fitting where a stocked one will not do.
VERIFY before issue
TRUE MEANS THE AVAILABILITY MATRIX AND THE GEOMETRY HAVE BEEN CHECKED AGAINST THE PUBLISHED TABLES, AND NOTHING MORE. It does not mean these are the current figures for the product and finish being specified, and it does not verify the CABLE bend radii, which come from a different source entirely (Sparkline’s own workbook).
fittings.what — the calculator’s own words, not a copy
The published radius is struck at the INNER edge of the ladder, derived twice and never assumed. First: the catalogue’s own `C` (centre-line length to the intersection) follows (R + W/2)·tan(θ/2) + 80 across every flat-bend row — the +W/2 term is the width’s contribution to the centreline, which it could not have if R were already the centreline. Second: `i`, which the catalogue defines in its own words as "measurement across the inner curve", is 2R·sin(θ/2) — the chord of an arc of radius R — across all 360 riser rows to 0.5 mm.
fittings.datum — the calculator’s own words, not a copy
Both riser types are modelled with the governing cable at the fitting’s INNER radius (Sparkline’s rule). On an outside riser the cables lie on the convex face, which the geometry above puts at R + the rail depth — so an outside riser may be more generous than reported by up to 100 mm (Topaz), 125 mm (Sapphire) or 150 mm (Emerald). It is never reported as better than it is.
fittings.outsideRiserConservative — the calculator’s own words, not a copy
Swifts cable tray bends are published with one fixed radius per fitting — the part number carries no radius (SRFB300G). That radius is not held here, so the required figure is reported and no tray fitting is named. Check it against the tray fitting’s own published radius.
fittings.trayNotHeld — the calculator’s own words, not a copy