Rule · CMS calculator

The drop, measured from the rung top

a choice

cms.rule.dropDatum

Where the height a cable needs on its way into a board is measured from: the top of the rung it lies on, to the gland plate.

Local graph

Leans on · 0Leaned on by · 1NothingThe drop into a switchboard — feeds, estimatedThe drop into aswitchboardfeedsThe drop, measuredfrom the rung top Leans on · 0Leaned on by · 1NothingThe drop into a switchboard — feeds, estimatedThe drop into aswitchboardfeedsThe drop,measured fromthe rung top Leans on · 0Leaned on by · 1NothingThe drop into a switchboard — feeds, estimatedThe drop into aswitchboardfeedsThe drop, measured from therung top

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

How the calculator uses it

Dropping, a cable needs its turn, then a straight, then the gland's length outside the plate; rising, its own diameter more, because the inside of the turn is then its top. Rising out of a cleat, it needs the cleat's lift as well: the cleat holds it that far above the rung top, so its turn starts there. The cable that needs the most height governs (the drop).

Watch for

The lift is added only when cables rise. Dropping, the lift only adds room, so it is left out.

Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung, the ladder above the board, 640 mm to the gland plate

The cable that needs the mostA1 · Ø 41.7 mm
Its radius, as the basis chosen334 mm to the cable axis
The turn, to its inner surface313 mm
The straight before the gland20 mm
The gland outside the plate84 mm (419CE-59)
Needed, from the rung top417 mm
VerdictOK — 223 mm in hand

Computed by the calculator for this run when this page was generated — not typed.