Rule · CMS calculator
Oval conduit fill
a choicecms.rule.ovalFill
How much of an oval conduit's inside area the cables may fill. No maker or standard publishes a figure for oval conduit, so this one is the calculator's own assumption — the share the flexible conduit maker uses — and the screen and the sheet say so.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The table we actually use
| Conduit | Cables at most % of the inside area | State |
|---|---|---|
| Oval conduit (PVC-U) | 40 |
1 row
How the calculator uses it
It is the space factor of an oval conduit run: the field starts here and can be changed per run. The area check sizes on it against the inside sizes, with the future spare kept clear on top.
Worked through on An oval conduit run — 3 × LSOH 1c 2.5mm², no future spare — a conduit starts with none
| 3 × LSOH 1c 2.5mm² | 13.8 mm² each, Ø4.2 mm |
|---|---|
| Their sum | 41.5 mm² |
| 16 × 10 mm oval conduit | 93.5 mm² inside (13.8 × 7.70 mm) × 40 % = 37.4 mm² — too small for 41.5 |
| 22.5 × 11 mm oval conduit | 165.4 mm² inside (20.0 × 9.17 mm) × 40 % = 66.2 mm² — covers 41.5 |
| The deepest cable | Ø4.2 mm, inside the 9.17 mm height — a deeper one could not lie in the oval at all |
| The conduit the engine chose | 22.5 × 11 mm — the smallest whose inside area, at the assumed fill, covers the cables |
| Verdict | PASS — 62.8 % of the usable area |
Computed by the calculator for this run when this page was generated — not typed.
VERIFY before issue
No maker or standard publishes a fill rule for oval conduit: the 40 % of its inside area is this calculator's own assumption, and the inside sizes are a distributor's (TLC Direct), not the maker's. Confirm both against the product before issue.
conduitOvalAssumed — the calculator’s own words, not a copy