The part of every size kept clear for cables added later. It is Sparkline's default, and a run may set its own. A conduit run starts with none — the owner's choice — and a figure typed into it is kept.

Local graph

Leans on · 0Leaned on by · 3NothingFill by area — feeds, publishedFill by areafeedsFill by width — feeds, publishedFill by widthfeedsConduit factors — feeds · off the conduit factor, publishedConduit factorsfeeds · off the conduit factorFuture spare Leans on · 0Leaned on by · 3NothingFill by area — feeds, publishedFill by areafeedsFill by width — feeds, publishedFill by widthfeedsConduit factors — feeds · off the conduit factor, publishedConduit factorsfeeds · off theconduit factorFuture spare Leans on · 0Leaned on by · 3NothingFill by area — feeds, publishedFill by areafeedsFill by width — feeds, publishedFill by widthfeedsConduit factors — feeds · off the conduit factor, publishedConduit factorsfeeds · off theconduit factorFuture spare

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The table we actually use

SettingKept clear %State
Default future spare30
Default on conduit0

2 rows

How the calculator uses it

The usable area, width or conduit factor is what is left after the spare is set aside — it comes off all three. On a ladder the spare is kept at the far side — the future-spare line — and no cleat may be dragged past it.

Worked through on A trunking run — 12 × LSOH 1c 6mm², 6 × LSOH 1c 10mm², 4 × LSOH 1c 16mm²

The size the engine chose50 × 50 mm
Its net internal area2,304.44 mm²
× the 45 % space factor × (1 − 30 % future spare)725.9 mm² usable
What the cables need693.4 mm²
VerdictPASS — 95.5 % of the usable area