Rule · CMS calculator
Future spare
a choicecms.rule.spareCapacity
The part of every size kept clear for cables added later. It is Sparkline's default, and a run may set its own. A conduit run starts with none — the owner's choice — and a figure typed into it is kept.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The table we actually use
| Setting | Kept clear % | State |
|---|---|---|
| Default future spare | 30 | |
| Default on conduit | 0 |
2 rows
How the calculator uses it
The usable area, width or conduit factor is what is left after the spare is set aside — it comes off all three. On a ladder the spare is kept at the far side — the future-spare line — and no cleat may be dragged past it.
Worked through on A trunking run — 12 × LSOH 1c 6mm², 6 × LSOH 1c 10mm², 4 × LSOH 1c 16mm²
| The size the engine chose | 50 × 50 mm |
|---|---|
| Its net internal area | 2,304.44 mm² |
| × the 45 % space factor × (1 − 30 % future spare) | 725.9 mm² usable |
| What the cables need | 693.4 mm² |
| Verdict | PASS — 95.5 % of the usable area |
Computed by the calculator for this run when this page was generated — not typed.