Check · CMS calculator
Fill by area
publishedcms.check.fillArea
The sizing check for a closed section, or for cables piled on an open one: the cables' areas against the area they may fill.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
It walks the sizes from the smallest and recommends the first whose usable area covers the cables — PASS where it does, FAIL where none can.
Worked through on A trunking run — 12 × LSOH 1c 6mm², 6 × LSOH 1c 10mm², 4 × LSOH 1c 16mm²
| The size the engine chose | 50 × 50 mm |
|---|---|
| Its net internal area | 2,304.44 mm² |
| × the 45 % space factor × (1 − 30 % future spare) | 725.9 mm² usable |
| What the cables need | 693.4 mm² |
| Verdict | PASS — 95.5 % of the usable area |
Computed by the calculator for this run when this page was generated — not typed.